Ipptr12 12 port video surge protection panel, Installation, Specification – Nitek IPPTR12 User Manual
Page 2

IPPTR12
12 Port Video Surge Protection Panel
INSTALLATION
The IPPTR12 must be properly installed to insure maximum
protection. The function of the IPPTR12 is to allow a surge to be routed
to ground and to clamp the protected equipment video inputs to a
minimum voltage.
There are three key points to remember when installing the
IPPTR12. First provide a low impedance connection between the IPPTR12
and your protected equipment. This is best done by keeping the PRO-
TECTED network cables as short as possible, ideally 3 feet or less.
Second the system should use a single ground point. Connect the
grounding stud of the IPPTR12 to a single ground point. A single ground
point is a proper building ground to which equipment grounds are
connected. Additionally, AC power line protectors should be used to
complete your surge protection strategy.
Finally, the UNPROTECTED cables should not be crossed with the
PROTECTED cables. Crossing cables could provide a path for surge currents
to bypass the IPPTR12 protection circuits.
SPECIFICATION
Size
1RU
Power Requirements
NONE REQUIRED
Connection Method
Standard RJ45 Nework Jack
(12 In - 12 Out)
Clamping Voltage
60v
Insertion Loss
<0.2dB
Temperature
-10C to +85C
For Use with
10/100 Networks and PoE Distribution
systems