DR Series Manual

20

4.0

Maintenance

4.0

Maintenance

Maintenance Checks

Main Burner

1

Gently use an air hose to blow any
accumulated dust and/or dirt off the heater.
Air hose pressure

must not exceed 30 psig.

2

Gently pass the air hose over the entire
exposed area of the ceramic. A distance of

2’ to 4’ from the unit is recommended.

NOTE: Blowing out the gasket material will
permanently damage the rayhead.

3

Gently place the air hose outlet into each

venturi tube and allow the air to flow for
approximately one minute.

4

See troubleshooting chart (page 21) if there
are any signs of burner malfunction. Replace
if necessary.

Pilot Burner

1

Remove pilot access door.

2

Use an air hose and gently blow the pilot
burner free of dust or debris.

Gas Supply

1

Periodically inspect the gas supply for signs

of corrosion or failure. Replace if necessary.

WARNING

!

Use protective glasses when cleaning

the heater.

Disconnect power to heater before

servicing.

Do not operate unit if repairs are

necessary. Do not operate unit

showing any signs of burner

malfunction. Call a professional for

assistance.

Avoid Equipment Failure.

Do not blow out heating elements
with high pressure air.

CAUTION

!

It is recommended that the following become a standard yearly procedure to obtain maximum operating

efficiency and trouble free operation.

During long periods of non-usage, remove or cover heater with a polyethylene bag and shut off gas

supply. If further service to the heater is desired, contact your representative or the factory.