beautypg.com

Detroit Radiant Products Company DR Series User Manual

Page 21

background image

DR Series Manual

20

21

4.0

Maintenance

Troubleshooting

Symptom

Code

Possible Cause

Corrective Action

Burning of gas-air

mixture inside

plenum (flashback).

A, B

A, B

A, B

A, B

A, B

• Heater mounted at incorrect angle.

• Excessive drafts.

• Gas leaking or blocked orifice/venturi.

• Separation of ceramic grids.

• Ceramic grids cracked.

• Mounting angle 20°-35° from horizontal.

• Relocate or shield from draft.

• Do not operate. Check with leak detector solution.

• Do not operate. Replace rayhead.

• Do not operate. Replace rayhead.

Delayed ignition.

A

A, B

A, B

A, B

A, B

• Electrode out of specification.

• Low gas pressure.

• Partially blocked orifice.

• Improper orifice size.

• Incorrect gas.

• See Figure 4.3.

• See Gas Supply section.

• Clean or replace.

• Consult dealer.

• Do not operate. See nameplate. Correct immediately.

Low ceramic surface

temperature, exces-

sive rollout or soot on

rods.

A, B

A, B

A, B

A, B

A, B

A, B

A, B

A, B

• Dirty or plugged rayhead ceramics.

• Partially blocked orifice.

• Low inlet gas pressure.

• Low manifold gas pressure.

• High manifold pressure.

• Foreign matter in venturi tube.

• Gas supply piping too small.

• Incorrect gas.

• See maintenance instructions.

• Remove and clean.

• See Gas Supply section.

• Adjust main valve regulator for 6” W.C.P. natural

gas, 10” W.C. P. propane.

• Adjust main valve regulator for 6” W.C.P. natural

gas, 10” W.C. P. propane.

• See Maintenance Section.

• Increase inlet pressure or replace.

• Do not operate. See nameplate. Correct immediately.

Control system

overheating.

A, B

A, B

• Heater not mounted correctly.

• Heater mounted too close to ceiling.

• Mounting angle 20°-35° from horizontal.

• Observe clearance to combustibles safety chart

located on heater reflector. Do not operate.

Gas odor.

A, B

B

• Loose pipe connection.

• Pilot not lit.

• Check all connections with leak-detector

solution, tighten as necessary.

• Cycle thermostat or manually light.

Heater cycles

repeatedly.

A, B

A

A, B

A, B

B

• Heater located in drafty area.

• Low gas pressure.

• Thermostat located in drafty area.

• Weak pilot flame.

• Defective flame detector.

• Relocate or shield from draft.

• See Gas Supply section for propane.

• Replace thermostat.

• Clean or adjust pilot.

• Replace.

Pilot on, no gas to

main burner.

B

• Weak pilot flame.

• No electrical power to unit.

• Pilot sensor element not located in pilot flame.

• Defective main valve solenoid.

• Defective pilot generator or thermocouple.

• Excessive thermostat wire length with millivolt

system.

• Manual valve off.

• Clean or adjust pilot.

• Check thermostat, manual switch or circuit

breaker.

• Locate upper 3/4 of element in pilot flame.

• Isolate. Ohm for resistance, replace if “0”.

• Replace.

• Wire not to exceed length provided by factory.

• Turn to “ON” position.

No spark; no ignition.

A

A

A

A

A

A

A

• Lack of 120V or 24V incoming voltage.

• Open high voltage wire.

• Improper electrode gap.

• Loose or open wire connection.

• Poor or no equipment ground.

• Unit in “safety lockout” mode.

• Defective “gas lighter” control.

• Proper voltage needed or repair wire.

• Isolate and ohm for resistance, replace if “0”.

• See Figure 4.3.

• Check all wires, tighten or replace.

• Trace ground wire for complete circuit back to

equipment ground from control.

• Interrupt power source, repeat trial for ignition.

• Verify proper voltage. Replace.

Heater lights, and

“locks out” after

approximately 10

seconds.

A

A

A

A

A

• Poor or no equipment ground.

• Polarity is reversed.

• Low gas pressure.

• Electrode not sensing.

• Heater mounted at incorrect angle.

• Check all connections, provide positive earth

ground.

• 120V to black, neutral to white.

• See Gas Supply section.

• Relocate or replace if defective.

• Mounting angle 20°-35° from horizontal.

Spark is present. No

main gas operation.

Unit “locks out”.

A

A

A

• Gas valve in “Off” position.

• Defective main valve solenoid.

• Defective “Gas lighter” control.

• Turn to “On” position.

• Isolate and check for resistance. Replace if “0”.

• Verify proper voltage. Replace.

Heater will not

shut off.

A, B

A, B

A, B

• Defective thermostat or wiring.

• Gas valve stuck open.

• High gas pressure.

• Replace or repair.

• Replace.

• See Gas Supply section.

Code: A - Direct Spark Ignition (NFS-2/PFS-2) B - Standing Pilot (NMV-2/PMV-2)

Chart 4.1

Troubleshooting Guide