0 troubleshooting guide – Detroit Radiant Products Company DES3 Series User Manual

Page 14

background image

14

DES3

Series

Is the ball valve in the

ON position?

Check that gas pressure is within

minimum and maximum inputs as

indicated on the heater’s rating plate.

Is gas pressure ok?

Does the fan

blower turn on?

4.0

Troubleshooting Guide

4.0

Troubleshooting Guide

Is the blower

obstructed?

Turn up thermostat.

Is the power at the

heater 120VAC?

No

Remove obstruction

and lubricate blower.

Does the igniter

spark?

Is the igniter

physically

damaged?

No

Yes

Replace igniter.

Yes

No

Find the source of the

electrical problem

.

Check the gap on the igniter.

Is the gap between

3/16 in. and 1/4 in.?

No

Adjust gap.

Yes

No

Yes

No

During the ignition

trial, does the gas

valve open?

Yes

Test for 120VAC at the gas
valve during valve opening

(typically 10 seconds after

power to the heater). Is there

120VAC to the valve?

No

Yes

The circuit board and/or

wiring harness could be
faulty. These should be

replaced.

No

Does the burner light?

No

Yes

Correct

problem.

Replace

gas valve.

Yes

No

Yes

Continued on page 16.

Yes

No

Turn knob on ball valve to

the ON position.

Yes