Rack/universal mount models, 6kva – MaxPower Corp UniStar P Rack User Manual
Page 5
Rack/Universal Mount Models
SC60021RM
SC60022RM
INPUT
Connection
Hardwire / Optional 6ft. Line Cord with L6 30P Plug
Voltage Range
160 -280Vac
Frequency
45 ~ 65 Hz
Phase/Wire
Single, Line + Common + Ground
Power Factor
Up to 0.99 at 100% Linear Load
Current THD
<5% at 100% Linear Load
OUTPUT
Connection
Hardwire
Hardwire
Voltage
208/120Vac or 240/120Vac
208/220/230/240Vac, Selectable 240/120, 208/120Vac
Voltage Adjustment
+/- 0%; +/- 1%; +/- 2%; +/- 3% For All Voltages
Voltage Regulation
+/- 2%
Capacity
6000VA/4200W
Parallel Capability
Redundancy or Capacity – 4 Units Maximum
Rated Power Factor
0.7 Lagging
Wave Form
Sine Wave, THD < 3% (no load to full load)
Frequency Stability
+/- 0.2% (Free Running)
Frequency Regulation
+/- 1 Hz
Transfer Time
0ms/instantaneous
Crest Factor
3:1
Effi ciency (AC to AC Nominal)
91%
Effi ciency (AC to AC ECO Mode)
Up to 97%
Leakage Current
< 3mA @ Full Load
DC Start
Yes
Cooling
Load Dependant Variable Speed Fans
DISPLAY, ALARMS, DIAGNOSTICS, COMMUNICATIONS & EMERGENCY FUNCTION
Status On LED + LCD
Line Mode, Backup Mode, ECO Mode, Bypass Supply, Battery Low,
Battery Bad/Disconnected, Overload, Transferring with interruption & UPS Fault
Readings On LED + LCD
Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage,
Battery Voltage & Unit’s Inner Temperature
Self-Diagnostics
Upon Power-on, Front Panel Setting & Software Control, 24 Hour self check
Audible Alarms and Visual
Line Failure, Battery Low, Transfer to Bypass, System Fault Conditions
Communications
RS232 Serial Port ( 2 slots available for optional SNMP/WEB, USB or Dry Contact Card)
Emergency Power Off (EPO)
Connection
Emergency Power Off shuts down UPS when activated by customer supplied EPO Circuit
PHYSICAL
Dimensions (H x W x D) inches
3.5 x 17.3 x 26 (2U)
Weight (lbs.)
53
Safety and Performance
UL1778, c-UL; CE – FCC Class A, EN 50091-2, EN 62040-2, EN61000-3,
IEC 61000 (various), IEC 62040, CISPR 22
EXTERNAL BATTERY PACK – Module 2, Plug Connected to UPS Module (Note 1)
*Model
SC-BP6000RM-1 (same battery used for extended run times)
Battery Run Time @ Full Load
8 minutes
Type
Sealed Lead Acid Maintenance Free, 20 each 12V/7AH, 240Vdc
Hot – Swap Batteries
Yes
Recharge Time
4 hours to 90%
Battery Connection
Plug Connector
Extended Run Time Battery Packs
Yes
Dimensions (H x W x D)
5.25" x 17.3" x 26" (3U)
Weight (lbs.)
119
OUTPUT TRANSFORMER / MANUAL BYPASS SWITCH - Module 3, (Hardwired to UPS Module (Note 1)
Output Voltage
208/120Vac or 240/120Vac
208/120Vac or 240/120Vac
Manual Bypass Switch
Make – Before - Break
Dimensions (H x W x D)
3.5" x 17.3" x 26.0" (2U)
Weight (lbs.)
93
OPTIONAL POWER DISTRIBUTION UNIT (PDU) for Model SC60021RM ONLY! – Module 4 Optional (Hardwired to Transformer Module)
Model
SC-6RMPDU1
SC-6RMPDU2
Input Voltage of UPS Module
208 or 240Vac
208 or 240Vac
Output Voltage through
Receptacles
208/120Vac or 240/120Vac
208Vac or 240Vac
Output Receptacles
(1) L6-30R, (1) L5-30R, (1) L5-20R, & (2) 5-15/2020R
(1) L6-30R, (1) L6-20R & (4) 6-20R
Dimensions (H x W x D)
3.5" x 12.8" x 2.8" (2U)
Weight (lbs.)
7
OPTIONAL COMMUNICATION Cards with Shutdown Software
SC-SNMP1
SNMP/WEB Network Card and Shutdown Software
SC-Contact/EPO
Dry Contact & EPO Card
SC-PK
Parallel Cable kit contains two RJ45 cables and miscellaneous hardware for paralleling
Note: (2) slots available; both cards can be used simultaneously; RS232 Port is disabled when communication cards are installed.
OPTIONAL EXTENDED BATTERY PACK CHARGER
SC-CHG-1000
1000W External Mount Battery Charger (1) charger
per every (2) External Battery Packs Required
6.6"W x 11.1"D x 3.4"H
7 lbs.
OPTIONAL PARALLEL DISTRIBUTION / BYPASS MODULE
(Note 2)
SC-PKIT-2
Parallel Distribution Bypass 60Amp for (2) UPS Modules
10.5"W x 9.5"D x 3.7"H
11 lbs.
SC-PKIT-4
Parallel Distribution Bypass 120Amp for (4) UPS Modules
10.5"W x 16.4"D x 3.7"H
20 lbs.
Notes:
Modules 1, 2 & 3 make up a complete hardwired 208/120Vac or 240/120Vac output system.
Parallel for capacity confi gurations can use (1) battery system sized for the ultimate capacity.
Parallel for redundancy confi gurations require (1) battery system for each UPS.
6kVA
Rack/Universal Mount Models