beautypg.com

Figure 2 – Mastercool 69300-220 TWIN TURBO REFRIGERANT RECOVERY SYSTEM User Manual

Page 4

background image

4

www.mastercool.com

its capacity. When the Recovery System is started vapor from the recovery tank is compressed and sent,
at high pressure, to HVAC or refrigeration system. As pressure builds, the liquid is “pushed” out of unit into
recovery tank. Vapor from recovery tank is “pulled” out of recovery tank, compressed, and then pressurizes
unit.
Note: Some systems may not have liquid service port. This prevents the push-pull technique from being
used.

Procedure for Push-Pull technique (Connect system per fig. 2 and following instructions).
1. Connect outlet port of Recovery System to vapor port of unit to be serviced. Use hoses with automatic or
manual valves on both ends to prevent refrigerant release when disconnecting.
2. Connect liquid port on unit to be serviced to liquid port on recovery tank. Recovery tank should be on a
scale that stops flow when 80% tank capacity is reached. This connection should be made with a
manifold gauge set with sight glass to verify liquid flow. Recovery tank must have a minimum pressure
rating of 38 bar (550 psi).
3. Connect vapor port of recovery tank to inlet port of Recovery System. Use hose with automatic or manual
valve on both ends.
4. Open valves on unit to be evacuated. Open valves on recovery tank.
5. On Recovery System, rotate outlet valve to

“OPEN” position. Rotate center valve to “RECOVER” position.

Rotate inlet valve to

“OPEN” position.

6. Start Recovery System.
7. Check the sight glass for the presence of liquid flow. When liquid stops flowing, rotate inlet valve on
Recovery System to

“CLOSED” position. When Recovery system is shut down due to vacuum, turn OFF

the power switch. Reconnect system for direct vapor recovery following instructions listed under
“Operating Guide for Direct Vapor or Liquid Recovery”.

30

25

20

15

10

5

0

0

200

250

300

350

400

450

150

100

100

90

80

70

60

50

40

30

20

10

110

130

120

140

150

350

50

0

PSI

PSI

BAR

BAR

R134a

MC

R134a

MC

40

60

50

70

80

30

20

10

0

190

18

0

17

0

160

150

140

130

120

110

100

90

80
70

60

40

20

0

34

1

2

3

4

5

6

7

8

9

10

18

0

0

10

-10

-20

-30

20

30

40

10

20

-20

30

40

50

60

70

80

90

100

11

0

-40 F

RETA

RD

In Hg

VAC

10

20

30

Liquid

Vapor

�����

���

R

Air Conditioning

or

Refrigeration System

Recovery

System

���������������������

���������������������

Approved

Recovery

Tank

Use Sight Glass

or

Manifold W/Sight Glass

FIGURE 2

This manual is related to the following products: