SINGLE PHASE POWER CONNECTIONS









REQUIREMENTS


The RA-121 can operate as a single phase unit using
using only 2 phases of a 3 phase power source. This
is NOT RECOMMENDED since it causes an
unbalanced load to the power source.

The unit should be connected to two hot lines which
are NOT the same phase.

The feed circuit must be able to supply 60 Amps for
each line.

CONNECTIONS

There are three terminals on the input terminal power
block (H1, H2, H3). When operating the RA-121 on
single phase power, the center (H2) terminal is not
used. The wires connected to the left side of the H2
terminal contain color coded sleeves (RED and
BLACK). These wires must be moved and distributed
to the H1 and H2 terminals. Remove the wires from
the H2 terminal and connect them to H1 and H2 such
that the sleeve color matches the wire colors on H1
and H2.

Connect the feed neutral to the NEUTRAL bus bar.

Connect the feed ground t

o the GROUND lug.

See the section SYSTEM POWER SETUP for
operation using single phase connections.































POWER IN

SINGLE PHASE 120/240 VAC

BLACK

RED

BLUE

BLUE

RED

MARKER

BLACK

MARKER

H1

H3

H2

NEUTRAL

GROUND

REAR OF RA-121

H2

NOT

USED

SINGLE PHASE POWER CONNECTIONS

WARNING

MAKE CERTAIN POWER IS REMOVED

FROM THE FEED CIRCUITS

BEFORE YOU BEGIN INSTALLATION.