RA – 121 RACK MOUNT ARCHITECTURAL DIMMER

Revision 0.93

OWNERS MANUAL

09/26/2011

www.lightronics.com

Lightronics Inc.

509 Central Drive Virginia Beach, VA 23454

Tel 757 486 3588

THREE PHASE POWER CONNECTIONS








REQUIREMENTS


True 120/208VAC three phase power must be supplied
to operate the RA-121 in the 3 phase configuration.
This means that the voltage across any two lines must
be 208 VAC. All three phases must be supplied. The
feed circuit must be able to supply 40 Amps for each
hot line.

THE UNIT WILL NOT OPERATE IN IT'S THREE
PHASE CONFIGURATION USING ONLY 2 LINES
OF A 3 PHASE 120/208 VAC SUPPLY CIRCUIT.


CONNECTIONS

Connect the 3 in hot feed lines to the 3 terminals on the
input power terminal block (H1, H2, H3).

Connect the feed neutral to the NEUTRAL bus bar.

Connect the feed ground t

o the GROUND lug.

See the section SYSTEM POWER SETUP for
operation using 3 phase connections.





































POWER IN

3 PHASE 120/208VAC

BLACK

RED

BLUE

BLUE

RED

MARKER

BLACK

MARKER

H1

H3

H2

NEUTRAL

GROUND

REAR OF RA-121

THREE PHASE POWER CONNECTIONS

WARNING

MAKE CERTAIN POWER IS REMOVED

FROM THE FEED CIRCUITS

BEFORE YOU BEGIN INSTALLATION.