Bills of materials, Piping with no valve, Wiring to lectrocount lcr-ii or lcr 600 – Liquid Controls Mechanical Eliminators User Manual
Page 27: Wiring to multiload toptech preset
27
PIPInG WITh no valve
To Supply/Storage
Tank
single head bulk Plant air
eliminator with optical sensor
bIlls of MaTerIals
a8170
BOM on page 25
Condulet box
w/ optical
sensor
81947
optical sensor
(sensor only)
WIrInG To leCTroCoUnT
lCr-II or lCr 600
Optical Sensor
Out8/Black (54)
In5/White (55)
+Vo/Red (56)
84040 or 81920
CPU Board
WIrInG To MUlTIload
ToPTeCh PreseT
To configure the single head bulk Plant air
eliminator with optical sensor to Multiload:
1. Set the number of seconds in Low Flow Time Alarm to
the desired time between Optical Sensor detection of air
and the valve closing to stop the flow .
2. Configure custom logic: Set Output Port 8 active (Control
Valve Enable) when Input Port 9 is active.
A89501 - 3"
A89541 - 4"
A89561 - 6"