beautypg.com

Laurel Electronics LTE SERIES TRANSMITTERS PULSE INPUT User Manual

Page 7

background image

- 7 -

7. LTE TRANSMITTER MAIN BOARD JUMPERS & FIELD WIRING

P4 Analog
output (standard)

P3 Solid state
relays (normally
open, standard)

P5 Signal
input &
excitation
output

Ana out -

1

Ana out +

2

Alarm 2 1
Alarm 2 2
Aalrm 1 3
Alarm 1 4

Signal

conditioner

board

3 Earth GND
2 AC neut or -DC
1 AC high or +DC

P1 Power input

E1

E4

a

b

E2

b

a

d

c

a

b

c

E3

RJ45

Ethernet

a

b

E7

An RJ45 Ethernet connector allows the transmitter to be connected directly to a computer, router,
switch or hub via an Ethernet cable. An isolated analog output and dual relays are also standard.

Jumpers on the main board allow selection of the following:

• Analog output (current or voltage).
• Power over Ethernet (PoE). Only available for main boards with the 10-48 Vdc power option.

Jumpers are preset if PoE is specified at the time of purchase.

• Excitation output. Note that attempting to draw more than the rated transducer excitation

output current will shut down the output.

Jumpers on analog signal conditioner boards are described in later manual sections.

To reset the transmitter (same as power-up), press the Reset button.

To reset communications to 9600 baud, command mode, Custom ASCII protocol, and Address 1,
place a jumper at E1 and power up the transmitter.

Analog Output

Jumpers

Current (0-20 mA)

E2 a + d

Voltage (0-10V)

E2 b + c

Power over Ethernet

Jumpers

Enabled

E7 a + b

Excitation Output

Jumpers

5V, 100 mA

E3 a + c; E4 a

10V, 120 mA

E3 a + c; E4 b

24V, 50 mA

E3 b, E4 none

Comm. Reset

Jumper

Jumper + power-up

E1