7. LTE TRANSMITTER MAIN BOARD JUMPERS & FIELD WIRING
P4 Analog
output (standard)
P3 Solid state
relays (normally
open, standard)
P5 Signal
input &
excitation
output
Ana out -
1
Ana out +
2
Alarm 2 1
Alarm 2 2
Aalrm 1 3
Alarm 1 4
Signal
conditioner
board
3 Earth GND
2 AC neut or -DC
1 AC high or +DC
P1 Power input
E1
E4
a
b
E2
b
a
d
c
a
b
c
E3
RJ45
Ethernet
a
b
E7
An RJ45 Ethernet connector allows the transmitter to be connected directly to a computer, router,
switch or hub via an Ethernet cable. An isolated analog output and dual relays are also standard.
Jumpers on the main board allow selection of the following:
• Analog output (current or voltage).
• Power over Ethernet (PoE). Only available for main boards with the 10-48 Vdc power option.
Jumpers are preset if PoE is specified at the time of purchase.
• Excitation output. Note that attempting to draw more than the rated transducer excitation
output current will shut down the output.
Jumpers on analog signal conditioner boards are described in later manual sections.
To reset the transmitter (same as power-up), press the Reset button.
To reset communications to 9600 baud, command mode, Custom ASCII protocol, and Address 1,
place a jumper at E1 and power up the transmitter.
Analog Output
Jumpers
Current (0-20 mA)
E2 a + d
Voltage (0-10V)
E2 b + c
Power over Ethernet
Jumpers
Enabled
E7 a + b
Excitation Output
Jumpers
5V, 100 mA
E3 a + c; E4 a
10V, 120 mA
E3 a + c; E4 b
24V, 50 mA
E3 b, E4 none
Comm. Reset
Jumper
Jumper + power-up
E1