4.0 SUPPORTED FUNCTION CODES

FC03: Read Holding Registers
Reads internal registers containing setup parameters (Scale, Offset, Setpoints, etc.)

FC10: Write Multiple Registers (FC10 = 16 dec)
Writes internal registers containing setup parameters (Scale, Offset, Setpoints, etc.)

FC04: Read Input Registers
Reads measurement values and alarm status. Returns values in 2's Complement Binary Hex
format without a decimal point. The displayed system decimal point can be read with FC03 at
address 0057. Use only odd Register Addresses and an even number of Registers.

Register
Address

TM Transmitter Response

------- -----------------------------------------------
00 01

Returns Hi word of Alarm status

00 02

Returns Lo word of Alarm status

00 03

Returns Hi word of Measurement value

00 04

Returns Lo word of Measurement value

00 05

Returns Hi word of Peak value

00 06

Returns Lo word of Peak value

00 07

Returns Hi word of Valley value

00 08

Returns Lo word of Valley value

FC05: Write Single Coil
Action command to meter

Output

Output

Address

Value

Action Command

-------

--------

----------------------------------------

00 01

FF 00

Transmitter Reset (No Response)

00 02

FF 00

Function Reset (Peak, Valley)

00 03

FF 00

Latched Alarm Reset

00 04

FF 00

Peak Reset

00 05

FF 00

Valley Reset

00 0C

FF 00

Tare Command (Weight Transmitter) (00 00 resets Tare)

FC08: Diagnostics
Checks communications between the Master and Slave, and returns the count in the Modbus
Slave counters (which are reset when the meter is reset).