beautypg.com

Laurel Electronics LTE SERIES TRANSMITTERS PULSE INPUT User Manual

Page 32

background image

- 32 -

Modbus ASCII Format

Byte Number

FC

Action

1

2

3

4

5

6

7

8

9

10

11

12

13

03
03

Request
Response

:
:

MA
MA

FC
FC

RA
NB

RA

DD*

NR

DD*

NR

LRC

LRC

CR

CR

LF

LF

04
04

Request
Response

:
:

MA
MA

FC
FC

RA
NB

RA

DD*

NR

DD*

NR

LRC

LRC

CR

CR

LF

LF

05
05

Request
Response

:
:

MA
MA

FC
FC

RA
RA

RA
RA

WW
WW

WW
WW

LRC
LRC

CR
CR

LF
LF

08
08

Request
Response

:
:

MA
MA

FC
FC

SF
SF

SF
SF

WW

DD

WW

DD

LRC
LRC

CR
CR

LF
LF

10
10

Request
Response

:
:

MA
MA

FC
FC

RA
RA

RA
RA

NR
NR

NR
NR

NB

LRC

DD*

CR

DD*

LF

LRC CR

LF

Exception

Response

:

MA FC

+80

EC LRC CR

LF

DD* = (DD DD) times NR (Number of Registers)

7.0 MESSAGE EXAMPLES

All examples are for Transmitter Address = 01 and No Parity.

Ser_4 ->

Addr ->

Action

Modbus RTU

010
001

Modbus ASCII

020
001

Restart Com-
munications

Request
Response*

010800010000B1CB
010800010000B1CB

:010800010000F6crlf
:010800010000F6crlf

Meter Reset

Request
Response

01050001FF00DDFA

None

:01050001FF00FAcrlf

None

Digital Reading

** ***

Request
Response

01040003000281CB

010404000009D67C4A

:010400030002F6crlf

:010404000009D618crlf

Write Setpoint
1 = +37.00***

Request
Response

0110000100020400000E743624

01030400000E74FE74

:0110000100020400000E7466crlf

:011000010002ECcrlf

Read Setpoint
1 = +37.00***

Request
Response

01030001000295CB

01030400000E74FE74

:010300010002F9crlf

:01030400000E7476crlf

* Suggested as first message after power-up. If transmitter is in Listen-Only mode, no response
is returned. ** Example while reading +25.18 *** Decimal point is ignored.

8.0 INTERNAL REGISTERS: Please refer to the full Modbus Protocol Communications Manual,

which is downloadable from our website.