beautypg.com

Laurel Electronics LTE SERIES TRANSMITTERS PULSE INPUT User Manual

Page 26

background image

- 26 -

13. DUAL RELAY OPERATION

Dual solid state relays are standard and can operate in a basic alarm mode, in a hysteresis band
mode, or in a deviation band mode. Setpoint operation is referenced to the digital reading in
engineering units that is internal to the transmitter.

Time

1000

D

ig

it

a

l

R

e

a

d

in

g

Setpoint

OFF

OFF

ON

Time

1000

Setpoint

OFF

ON

ON

D

ig

it

a

l

R

e

a

d

in

g

Active High Basic Alarm Active Low Basic Alarm

In basic alarm, the relay changes state automatically when the reading rises above a limit, and
changes back automatically when the reading falls below that limit. A red LED indicates that the
relay is in an alarm condition. The alarm can be programmed to be active high or active low.

Time

R

e

a

d

in

g

1050

950

Pass

Fail

Fail

Time

1050

Setpoint = 1000
Hysteresis value = 50

Heater

OFF

R

e

a

d

in

g

ON

ON

ON

OFF

OFF

950

Setpoint = 1000
Deviation value = 50

1000

1000

Pass

Hysteresis Band Alarm Deviation Band Alarm

In hysteresis band alarm, the relay closes (or opens) when the reading goes above the
setpoint plus one hysteresis value, and opens (or closes) when the reading falls below the
setpoint less one hysteresis value. A narrow hysteresis band is often used to minimize relay
chatter. A wide hysteresis band can be used for on-off control.

In deviation band alarm, the relay actuates when the reading falls within the deviation band,
and de-actuates when the reading falls outside. A deviation value (such as 50 counts) is set up
on both sides of the setpoint. Passbands are often used for component testing.