Configuration

Sealevel Systems SeaLINK+8 Page

6

Interface Biasing Configuration

The last four positions for each port are used to select the line termination and
bias settings. Refer to the chart below for specific switch settings of the three
supported electrical interface modes. Note that this chart appears in the silk
screen on the board as well.

PD = 1Kohm pull-down resistor connected to RX-

RS-232 mode = always OFF

RS-422 mode = always ON

RS-485 mode = ON if not provided by another device on the bus


PU = 5.1Kohm pull-up resistor connected to CTS+

RS-232 mode = always OFF

RS-422 mode = always ON

RS-485 mode = always ON


PU = 1Kohm pull-down resistor connected to RX+

RS-232 mode = always OFF

RS-422 mode = always ON

RS-485 mode = ON if not provided by another device on the bus


T = 120ohm terminating resistor connected between RX+ and RX-

RS-232 mode = always OFF

RS-422 mode = always ON

RS-485 mode = ON if physically located at one end of bus

SWITCH

232

INTERFACE BIASING

422
485

OFF OFF

PD

PU

ON

ON

ON

ON

OFF OFF

PU

T

ON

ON*

ON

ON

* = IF END OF 485 BUS

Figure 3 - Electrical Interface Termination and Biasing Selection

Technical Note

Contrary to some of our other products, there are no provisions on board for
looping TX+ to RX+ and TX- to RX- for 2-wire RS-485 mode. These
connections must be made externally inside the mating DB-9 connector. Refer
to the RS-422 pinout diagram for the appropriate pin numbers.