beautypg.com

Dsca, High performance signal conditioners, Dsca specifications – Impulse DSCA45 User Manual

Page 2: Ordering information

background image

High Performance Signal Conditioners

DSCA

Visit our website www.dataforth.com

153

DSCA

Specifications

Input

Range

0 to 100kHz max

Threshold

Zero Crossing

Minimum Input

60mVp-p

Maximum Input

350Vp-p

Minimum Pulse Width

4µs

TTL Input Low

0.8V max

TTL Input High

2.4V min

Hysteresis

Zero Crossing

40mV

TTL

1.5V

Resistance

100k

Protection

Continuous

240Vrms max

Transient

ANSI/IEEE C37.90.1

Output Range

See Ordering Information

Adjustability

±5% Zero & Span

Load Resistance (I

OUT

)

600

max.

Current Limit

8mA (V

OUT

), 30mA (I

OUT

)

Output Protection

Short to Ground

Continuous

Transient

ANSI/IEEE C37.90.1

Ripple

<0.20% Span at input >2% Span

Accuracy

(1)

±0.05% Span

vs. Temperature

±40ppm/°C (Zero & Span)

Nonlinearity

±0.02% Span

Isolation (Common Mode)

Input to Output, Input to Power

Continuous

1500Vrms max

Transient

ANSI/IEEE C37.90.1

Output to Power

Continuous

50VDC max

Rejection (50-60Hz Common Mode)

120dB

Response Time (0 to 90%)

DSCA45-01, -02, -03

310ms, 175ms, 50ms

DSCA45-04, -05, -06

30ms, 30ms, 15ms

DSCA45-07, -08

15ms, 1.5ms

Field Excitation

+5.1V ±5% at 8mA max

Power Supply

Voltage

19 to 29VDC

Current

60mA (V

OUT

), 80mA (I

OUT

)

Sensitivity

±0.0002%/%

Protection

Reverse Polarity

Continuous

Transient

ANSI/IEEE C37.90.1

Environmental

Operating & Storage Temp. Range

-40°C to +80°C

ATEX Group II, Category 3

-20°C to +40°C

Relative Humidity

0 to 95% noncondensing

Emissions EN61000-6-4

ISM, Group 1

Radiated, Conducted

Class A

Immunity EN61000-6-2

ISM, Group 1

RF

Performance A ±0.05% Span Error

ESD, EFT, Surge, Voltage Dips

Performance B

Mechanical Dimensions

2.95" x 0.89" x 4.13"

(h)(w)(d)

(75mm x 22.5mm x 105mm)

Mounting

DIN EN50022-35x7.5

or -35x15 rail

Module

Typical at T

A

=+25°C and +24V supply voltage

DSCA45

Ordering Information

Model

Input Range

Output Range

†

DSCA45-01

0-500Hz

2, 3, 4

DSCA45-02

0-1kHz

2, 3, 4

DSCA45-03

0-2.5kHz

2, 3, 4

DSCA45-04

0-5kHz

2, 3, 4

DSCA45-05

0-10kHz

2, 3, 4

DSCA45-06

0-25kHz

2, 3, 4

DSCA45-07

0-50kHz

2, 3, 4

DSCA45-08

0-100kHz

2, 3, 4

NOTES:

(1) Includes nonlinearity, hysteresis and repeatability.

Output Range

Part No. Suffix

Example

1. -10V to +10V

NONE

N/A

2. 0V to +10V

NONE

DSCA45-01

3. 4 to 20mA

C

DSCA45-01C

4. 0 to 20mA

E

DSCA45-01E

†

††

†

†

Output Ranges Available

Installation Notes:

1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The

Area is Known to be Non-Hazardous.