Dsca, High performance signal conditioners, Dsca specifications – Impulse DSCA45 User Manual
Page 2: Ordering information
![background image](/manuals/335884/2/background.png)
High Performance Signal Conditioners
DSCA
Visit our website www.dataforth.com
153
DSCA
Specifications
Input
Range
0 to 100kHz max
Threshold
Zero Crossing
Minimum Input
60mVp-p
Maximum Input
350Vp-p
Minimum Pulse Width
4µs
TTL Input Low
0.8V max
TTL Input High
2.4V min
Hysteresis
Zero Crossing
40mV
TTL
1.5V
Resistance
100k
Ω
Protection
Continuous
240Vrms max
Transient
ANSI/IEEE C37.90.1
Output Range
See Ordering Information
Adjustability
±5% Zero & Span
Load Resistance (I
OUT
)
600
Ω
max.
Current Limit
8mA (V
OUT
), 30mA (I
OUT
)
Output Protection
Short to Ground
Continuous
Transient
ANSI/IEEE C37.90.1
Ripple
<0.20% Span at input >2% Span
Accuracy
(1)
±0.05% Span
vs. Temperature
±40ppm/°C (Zero & Span)
Nonlinearity
±0.02% Span
Isolation (Common Mode)
Input to Output, Input to Power
Continuous
1500Vrms max
Transient
ANSI/IEEE C37.90.1
Output to Power
Continuous
50VDC max
Rejection (50-60Hz Common Mode)
120dB
Response Time (0 to 90%)
DSCA45-01, -02, -03
310ms, 175ms, 50ms
DSCA45-04, -05, -06
30ms, 30ms, 15ms
DSCA45-07, -08
15ms, 1.5ms
Field Excitation
+5.1V ±5% at 8mA max
Power Supply
Voltage
19 to 29VDC
Current
60mA (V
OUT
), 80mA (I
OUT
)
Sensitivity
±0.0002%/%
Protection
Reverse Polarity
Continuous
Transient
ANSI/IEEE C37.90.1
Environmental
Operating & Storage Temp. Range
-40°C to +80°C
ATEX Group II, Category 3
-20°C to +40°C
Relative Humidity
0 to 95% noncondensing
Emissions EN61000-6-4
ISM, Group 1
Radiated, Conducted
Class A
Immunity EN61000-6-2
ISM, Group 1
RF
Performance A ±0.05% Span Error
ESD, EFT, Surge, Voltage Dips
Performance B
Mechanical Dimensions
2.95" x 0.89" x 4.13"
(h)(w)(d)
(75mm x 22.5mm x 105mm)
Mounting
DIN EN50022-35x7.5
or -35x15 rail
Module
Typical at T
A
=+25°C and +24V supply voltage
DSCA45
Ordering Information
Model
Input Range
Output Range
DSCA45-01
0-500Hz
2, 3, 4
DSCA45-02
0-1kHz
2, 3, 4
DSCA45-03
0-2.5kHz
2, 3, 4
DSCA45-04
0-5kHz
2, 3, 4
DSCA45-05
0-10kHz
2, 3, 4
DSCA45-06
0-25kHz
2, 3, 4
DSCA45-07
0-50kHz
2, 3, 4
DSCA45-08
0-100kHz
2, 3, 4
NOTES:
(1) Includes nonlinearity, hysteresis and repeatability.
Output Range
Part No. Suffix
Example
1. -10V to +10V
NONE
N/A
2. 0V to +10V
NONE
DSCA45-01
3. 4 to 20mA
C
DSCA45-01C
4. 0 to 20mA
E
DSCA45-01E
Output Ranges Available
Installation Notes:
1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The
Area is Known to be Non-Hazardous.