DSCA45

Frequency Input Signal Conditioners

Description

Each DSCA45 frequency input module provides a single channel of frequency

input which is isolated and converted to a standard analog voltage or current

output (Figure 1).
The frequency input signal can be a TTL level or zero-crossing signal. Terminal

7 (-IN) on the field-side terminal block is the “common” or ground connection

for input signals. A TTL signal is connected from terminal 6 (+IN) to terminal 7

(-IN), while a zero-crossing signal is connected from terminal 5 (+EXC) to

terminal 7 (-IN). Input circuitry for each of the signal types has hysteresis built

in. An input signal must cross entirely through the hysteresis region in order to

trigger the threshold comparator.
A +5.1V excitation is available for use with magnetic pick-up or contact-closure

type sensors. The excitation is available on terminal 8 (-EXC) with return at

terminal 7 (-IN).
Module output is either voltage or current. For current output models a dedicated

loop supply is provided at terminal 3 (+OUT) with loop return located at terminal

4 (-OUT). The system-side load may be either floating or grounded.
Special input circuits provide protection against accidental connection of power-

line voltages up to 480VAC and against transient events as defined by ANSI/

IEEE C37.90.1. Protection circuits are also present on the signal output and

power input terminals to guard against transient events and power reversal.

Signal and power lines are secured to the module using screw terminals which

are pluggable terminal blocks for ease of system assembly and reconfiguration.
DSCA45 modules have excellent stability over time and do not require

recalibration, however, both zero and span settings are adjustable to accom-

Figure 1: DSCA45 Block Diagram

Features

• Accepts Frequency Inputs of 0 to 100kHz
• Industry Standard Output of Either 0-10V,

0-20mA, or 4-20mA

• ±0.05% Factory Calibrated Accuracy
• Adjustable Zero (±5%) and Span (±5%)
• 1500Vrms Transformer Isolation
• Input Overload Protected to 240VAC

Continuous

• ANSI/IEEE C37.90.1 Transient Protection
• Mounts on Standard DIN Rail
• C-UL-US Listed
• CE and ATEX Compliant

modate situations where fine tuning is desired. The adjustments are made using

potentiometers located under the front panel label and are non-interactive for

ease of use.