beautypg.com

Dsca, High performance signal conditioners, Dsca specifications – Impulse DSCA49 User Manual

Page 2: Ordering information

background image

High Performance Signal Conditioners

DSCA

Visit our website www.dataforth.com

157

DSCA

Specifications

Module

Typical at T

A

=+25°C and +24V supply voltage

DSCA49-04, -05, -06

Output Range

0 to +10V or -10 to +10V

Over Range Capability

5%

Output Drive

±50mA max.

Output Resistance

0.5

Output Current Limit

75mA

Output Protection

Continuous

240Vrms max

Transient

ANSI/IEEE C37.90.1

Input Range

0V to +10V or -10V to +10V

Input Resistance

Normal

50M

Power Off

65k

Overload

65k

Input Protection

Continuous

±35V max

Transient

ANSI/IEEE C37.90.1

CMV, Output to Input, Output to Power

Continuous

1500Vrms max

Transient

ANSI/IEEE C37.90.1

CMV, Input to Power

Continuous

50VDC max

CMR (50Hz or 60Hz)

110dB

Accuracy

(1)

±0.05% Span

Nonlinearity

±0.02% Span

Adjustability

±5% Zero and Span

Stability

Zero

±20ppm/°C

Span

±40ppm/°C

Output Noise, 100kHz Bandwidth

2mVrms

Bandwidth, –3dB

1kHz

NMR

100dB/Decade Above 1kHz

Response Time, 90% Span

425µs

Power Supply

Voltage

19 to 29VDC

Current

80mA

Sensitivity

±0.0003%/%

Protection

Reverse Polarity

Continuous

Transient

ANSI/IEEE C37.90.1

Environmental

Operating Temp. Range

–40°C to +80°C

ATEX Group II, Category 3

–20°C to +40°C

Storage Temp. Range

–40°C to +80°C

Relative Humidity

0 to 95% Noncondensing

Emissions EN61000-6-4

ISM, Group 1

Radiated, Conducted

Class A

Immunity EN61000-6-2

ISM, Group 1

RF

Performance A ±0.05% Span Error

ESD, EFT, Surge, Voltage Dips

Performance B

Mechanical Dimensions

2.95" x 0.89" x 4.13”

(h)(w)(d)

(75mm x 22.5mm x 105mm)

Mounting

DIN EN 50022 -35x7.5

Ordering Information

DSCA49-04

0V to +10V

-10V to +10V

DSCA49-05

-10V to +10V

-10V to +10V

DSCA49-06

-10V to +10V

0V to +10V

NOTES:

(1) Includes nonlinearity, hysteresis and repeatability.

Model

Input Range

Output Range

Installation Notes:

1.) This Equipment is Suitable for Use in Class I, Division 2, Groups A, B, C, D, or Non-Hazardous Locations Only.
2.) Warning - Explosion Hazard - Substitution of Components May Impair Suitability for Class I, Division 2.
3.) Warning - Explosion Hazard - Do Not Disconnect Equipment Unless Power Has Been Switched Off or The

Area is Known to be Non-Hazardous.