beautypg.com

Impulse DSCA49 User Manual

Dsca49, Voltage output signal conditioners, Dsca

background image

High Performance Signal Conditioners

DSCA

For information call 800-444-7644

156

DSCA49

Voltage Output Signal Conditioners

Description

Each DSCA49 voltage output module provides a single channel of analog

output. The input signal is buffered, isolated, filtered and converted to a voltage

output. Signal filtering is accomplished with a five-pole filter which provides

100dB per decade of attenuation above 1kHz. An anti-aliasing pole is located

on the system side of the isolation barrier, and the other four poles are on the

field side. After the initial system-side filtering, the input signal is chopped by a

proprietary chopper circuit. Isolation is provided by transformer coupling, again

using a proprietary technique to suppress transmission of common mode spikes

or surges.
Special output circuits provide protection against accidental connection of

power-line voltages up to 240VAC and against transient events as defined by

ANSI/IEEE C37.90.1. Protection circuits are also present on the signal input and

power input terminals to guard against transient events and power reversal.

Signal and power lines are secured to the module using screw terminals which

are in pluggable terminal blocks for ease of system assembly and reconfiguration.
The modules have excellent stability over time and do not require recalibration,

however, zero and span settings are adjustable up to ±5% to accommodate

situations where fine-tuning is desired. The adjustments are made using

potentiometers located under the front panel label and are non-interactive for

ease of use.

Figure 1: DSCA49 Block Diagram

Features

• Accepts High Level Voltage Input
• Provides High Level Voltage Outputs to

±10V at 50mA

• ANSI/IEEE C37.90.1
• 1500Vrms Transformer Isolation
• ±0.05% Accuracy
• ±0.02% Linearity
• Output Protected to 240VAC Continuous
• True 3-Way Isolation
• Wide Range of Supply Voltage
• 100dB CMR
• Easily Mounts on Standard DIN Rail
• C-UL-US Listed
• CE and ATEX Compliant