beautypg.com

Impulse SCM5B33 User Manual

Scm5b33, Isolated true rms input modules, Scm5b

background image

For information call 800-444-7644

10

Isolated Analog Signal Conditioning Products

SCM5B

SCM5B33

Isolated True RMS Input Modules

Description

Each SCM5B33 True RMS input module provides a single channel of AC input

which is converted to its True RMS DC value, filtered, isolated, amplified, and

converted to a standard process voltage or current output (Figure 1).
The SCM5B modules are designed with a completely isolated computer side

circuit which can be floated to ±50V from Power Common, pin 16. This complete

isolation means that no connection is required between I/O Common and Power

Common for proper operation of the output switch. If desired, the output switch

can be turned on continuously by simply connecting pin 22, the Read-Enable

pin, to I/O Common, pin 19.
The field voltage or current input signal is processed through a pre-amplifier and

RMS converter on the field side of the isolation barrier. The converted DC signal

is then chopped by a proprietary chopper circuit and transferred across the

transformer isolation barrier, suppressing transmission of common mode

spikes and surges. The computer side circuitry reconstructs, filters and converts

the signal to industry standard outputs. Modules are powered from

+5VDC, ±5%.
For current output models, an external loop supply of 4.2V to 26V is required.

The loop supply connection, with series load, is between Pin 20 (+) and

Pin 19 (-).

Figure 1: SCM5B33 Block Diagram

Features

• Interfaces RMS Voltage (0 – 300V) or RMS

Current (0 – 5A)

• Designed for Standard Operation with

Frequencies of 45Hz to 1000Hz

(Extended Range to 20kHz)

• Compatible with Standard Current and

Potential Transformers

• Industry Standard Output of either 0-1mA,

0-20mA, 4-20mA, 0-5V or 0-10VDC

• ±0.25% Factory Calibrated Accuracy

(Accuracy Class 0.2)

• 1500Vrms Continuous Transformer Isolation
• Input Overload Protected to 480V Max

(Peak AC & DC) or 10A RMS Continuous

• ANSI/IEEE C37.90.1 Transient Protection
• CSA Certified, CE and ATEX Compliant