6 time zone operation – Controlled Products Systems Group 1506-080 User Manual
Page 21
Page 21
3.6
Time Zone Operation
The entry system has two time zone inputs. By using an external timer or switch, access can be
denied to a group of four-digit entry codes during desired lockout times. Four-digit entry codes that fall
numerically within a time zone boundary will cause a check of the time zone input when the code is
entered. If time zone 1 is activated (switch closure across terminals 3 and 11), four-digit entry codes
that are within the time zone 1 boundaries will be denied access. If time zone 2 is activated (switch
closure across terminals 4 and 11), four-digit entry codes that are within time zone 2 boundaries will
be denied access. Time zone boundaries may overlap each other. Five-digit entry codes are not time
zone restricted.
Time Zone 1
Time Zone 2
Entry codes
1999 and
lower are
not time
zone
restricted.
Lower Bou
n
d
a
ry
2000
Entry codes 2000
thru 3000 are
restricted by time
zone 1.
U
p
pe
r Bo
un
da
ry
3000
Entry codes
3001 thru
3999 are not
time zone
restricted.
Lower Bou
n
d
a
ry
4000
Entry codes 4000
thru 5000 are
restricted by time
zone 2.
U
p
pe
r Bo
un
da
ry
5000
Entry
codes
5001 and
higher are
not time
zone
restricted.
Time Zone 1
TZ 2 Lower B
ound
ary
2500
Entry codes
2500 thru
2999 are
restricted bt
TZ 1 and TZ
2.
TZ 1 Upp
er B
ound
ary
3000
Entry codes
3000 thru 3500
are restricted by
TZ 2 only.
TZ 2 Upp
er B
ound
ary
3500
Entry codes
1999 and
lower are
not affected
by time
zones.
TZ 1 Lower B
ound
ary
2000
Entry codes
2000 thru 2499
are restricted by
TZ 1 only.
Time Zone 2
Entry
codes
3501 and
higher are
not time
zone
restricted.