Installing the UV Lamp,

Continued

Position Glo-
Cap

The Glo-Cap must be properly placed on the headpiece for the UV
disinfection unit to work. Follow the steps below to position the Glo-Cap.

Step Action

1

Align the tab on the Glo-Cap with the middle tab on the transparent clip.

2

Lower the Glo-Cap onto the headpiece until it clicks into place. If it does not
click into place, make sure that the tabs on the Glo-Cap are not over the raised
tabs on the headpiece. If they are, turn the Glo-Cap. When properly installed, the
Glo-Cap will not separate from the headpiece.












Attach sensor

The UV system includes a sensor port and sensor assembly. Attach the
sensor assembly to the sensor port on the disinfection chamber, as shown
below. Hand-tighten the sensor assembly onto the threaded nipple by
rotating clockwise until you have a proper seal. Do not use tools on the sensor
assembly. (Note: Ensure O-ring is seated properly against lens before
installing sensor assembly to sensor port.