5 setup – sensors up to software3.99, 1 common adjustment menu for all signal outputs, 5setup - sensors up to software 3.99 – Burkert Type 8186 User Manual
Page 11

5
Setup - Sensors up to software 3.99
5
.1 Common adjustment menu for all signal
outputs
Through the parameter adjustment the instrument is adapted to the
application conditions. The parameter adjustment is carried out via an
adjustment menu.
Information:
In this operating instructions, all general parameters are described.
Additional instrument-specific parameters are described in the
operating instructions of the respective sensor.
The following presentations are available in the measured value
display:
l
Level as digital value, sensor TAG
l
Level as digital value and bar graph, sensor TAG
l
Only with pressure transmitters: Level or pressure as digital value,
temperature value
With [->] you select different presentations of the measured value.
From each of these presentations, you can reach with [OK] the menu
overview. With [ESC] you move from the menu overview again to the
measured value indication.
The main menu is divided into five sections with the following
functions:
▶
Basic adjustment
Display
Diagnostics
Service
Info
To damp process-dependent measured value fluctuations, you have to
set an integration time of 0 … 999 s in this menu item.
Depending on the sensor type, the factory setting is 0 s or 1 s.
Damping
0
s
In this menu item you select the linearization curve:
l
Linear
l
Horizontal cylindrical tank
l
Spherical tank
l
User programmable
Measured value indica-
tion
Main menu
Basic adjustment/Damp-
ing
Basic adjustment/Linea-
rization curve
Indicating and adjustment module
11
5
Setup - Sensors up to software 3.99
41787
-
EN
-