6 set up, 1 general information, 2 adjustment elements – Burkert Type 8111 User Manual
Page 19: 6set up

6
Set up
6
.1 General information
The figures in brackets refer to the following illustrations.
The switching condition of the electronics can be checked with closed
housing cover (control lamp). In the basic setting, products with a
density > 0.7 g/cm³ (0.025 lbs/in³) can be detected. For products with
lower density, the switch must be set to > 0.5 g/cm³ (0.018 lbs/in³).
On the electronics module you will find the following indicating and
adjustment elements:
l
Signal lamp (1)
l
DIL switch for characteristics reversal - min./max. (2)
l
DIL switch for sensitivity adjustment (3)
l
Simulation key (4)
Note:
For test purposes, immerse the tuning fork of LEVEL SWITCH 8111
always in liquids. Do not test the function of LEVEL SWITCH 8111 with
your hand. This can damage the sensor.
6
.2 Adjustment elements
1
5
2
3
4
Fig. 10: Oscillator SWE60N - NAMUR output
1
Signal lamp (LED)
2
DIL switch for characteristics reversal
3
DIL switch for sensitivity adjustment
4
Simulation key
5
EMC filter element
Function/Configuration
LEVEL SWITCH
8111 • with NAMUR output
19
6 Set up
32048
-