beautypg.com

Flowline LD35 DeltaSpan User Manual

Page 14

background image

14 of 16 

MN301035 

Rev B 

INSTALLATION 

Step Nine 

The  LD34  /  LD35  series  are  designed  to  operate  while  submerged  in  the  actual 
application liquid.  Avoid installing the level transmitter along the bottom of the tank as 
materials such as sludge will build up and coat/cover the transmitter.  This also includes 
any debris that will settle along the bottom of the tank.  In these applications, it is best 
to suspend the transmitter above the highest level of sludge/debris that will occur. 

1. Location: Select a location where the temperature of the transmitter will be 

between 0 and 176°F (‐18 to 80°C). Distance from the receiver is limited only by 
total loop resistance. 

2. Position:  The  transmitter  is  not  position  sensitive.  However  all  standard  models  are  originally 

calibrated with the unit in a position with the pressure connection downward. Although they can be 
used  at  other  angles,  for  best  accuracy  it  is  recommended  that  units  be  installed  in  the  position 
calibrated at the factory. 

3. Mounting:  The  transmitter  can  be  mounted  via  several  methods.    It  can  be  suspended  from  the 

electrical  cable,  or  it can  be  placed  resting  on the  bottom  of  the  tank in  either  horizontal  or  vertical 
orientation. 

Interference:  The DeltaSpan™ is designed to operate under the surface of the liquid in 
the tank.  Avoid installations where other tank requirements will cause the transmitter 
to move or swing.  For example: a mixer blade could cause the level transmitter to whip 
around within the tank.  An alternative would be to move the transmitter to a more 
stable section of the tank or to install the LD34/LD35 series inside a still well/drop tube.  
The still well/drop pipe will minimize the effects created by the mixer.  

Termination:  The cable for the DeltaSpan™ is typically terminated at a junction box 
located on top of the tank.  Since the vent tube is contained within the cable, the 
pressure within the junction box must always be the same as the reference (typically 
atmospheric) pressure for the liquid.  The inside of the junction box must be clean, dry and free of moisture.  
Add the optional pressure fitting (LD90‐_001) to complete the package.  The LD90‐_001 
features a 2” NPT thread for mounting and a liquid tight connector to seal the cable 
interface. 

Note:  Use caution when sealing the cable at the top of the tank.  The ventilation tube 
must  be  open  and  free  to  allow  air  to  flow  back  to  the  pressure  diaphragm.    Avoid 
blocking  the  ventilation  tube  by  compressing  the  cable.    Always  keep  the  cable 
termination  clean,  dry  and  free  of  moisture  and  prevent  liquid  from  entering  the  vent 
tube. 

Note:  A vent Filter is provided on the end of the vent tube.  If the application requires 
the vent tube to be cut to length, then remove the vent filter and place on the end of the new end of the vent 
tube. 

Note: For extra protection against high humidity environments, Flowline offers the LD90‐3000 desiccant filter 
that can be attached to the vent tube. 
 

 

This manual is related to the following products: