beautypg.com

Flowline LD35 DeltaSpan User Manual

Page 10

background image

10 of 16 

MN301035 

Rev B 

GETTING STARTED (continued) 

Step Six 

How to configure a panel meter when a pressure transmitter is used? 
This  method  works  with  the  LI55  series,  LI25  Series,  LI10  Series  and  LI50  Series.    These  panel  meters  are 
configured  using  the  SCALE  function.    The  SCALE  function  typically  has  four  settings.    These  settings  are  as 
follows: 

Settings 

Default 

Represents 

Typical Setting 

Input 1 

04.000 

Input current @ Empty 

04.000 (mA) 

Display 1 (Empty) 

04.000 

Display value @ Empty 

Empty value 

Input 2 

20.000 

Input current @ Full 

20.000 

Display 2 (Full) 

20.000 

Display value @ Full 

Full Value (mA) 

Remember,  pressure  transmitters  are  configured  so  0  psi  =  4  mA  and  the  maximum  psi  =  20  mA.    Most 
pressure  transmitter  applications  will  not  use  the  full  range  of  the  transmitter  and  requires  you  to 
proportionally scale the current output of the pressure transmitter.  Therefore, a full tank will typically have a 
current less than 20 mA.  The goal in configuring the panel meter is to calculate the current when the tank is 
full.  To do this, use the following formula: 

(Full Tank Height / Maximum Liquid Height) x 16 + 4 = Current at Full 

Example:  A 40 foot tank with a SG = 0.9 will have a maximum pressure of 15.58 psi.  A 20 psi sensor is selected 
for use.  The Maximum Liquid Height = (20 psi x 2.31’/psi) / 0.9 = 51.33 feet.  Using the above formula, the 
Current at Full = [(40 feet / 51.33 feet) x 16 + 4] = 16.468 mA. 

The Current at Full will be used as the Input 2 value.  This means that when the display reads a current equal 
to Current at Full, it will display the Full value (Display 2 value).  The panel meter will be configured as follows: 

Settings 

Configured 

Input 1 

04.000 

Display 1 

Empty 

Input 2 

16.468 

Display 2 

Full 

Note:  The values for empty and full represent what the display will show when the tank is either Empty or Full.  
Empty and Full must be the same units (example: Gallons, Inches, percent).  

 The default for the Input 1 is 4 mA and typically will never be changed.     
 Typically, the Empty setting will be what is in the tank when it is empty (example: 000.0 Gallons, 000.0 

inches, 000.0 feet etc.).   

 The Full setting will be what is in the tank when it is full (example: 500.0 Gallons, 120.0 inches, 10.0 

feet, etc.).  

 

 

This manual is related to the following products: