DE DIETRICH AFC 18 - AFC 24 - AFC 30 User Manual
Page 37
Code Faults
Cause
of the
fault
Description
Checking / solution
D05
OUTSI.S.FAIL.
SCU
Outside temperature sensor fault
Remarks:
The boiler operates on BOILER
MAX
temperature.
The valve setting is no longer
ensured but monitoring the
maximum temperature of the circuit
after the valve is ensured.
Valves may be manually operated.
Reheating the domestic hot water
remains ensured.
Bad connection
Sensor fault
4
Contact the professional who takes care of
maintenance of the appliance
D07
SYST.SENS.FAIL.
SCU
System sensor fault
Bad connection
Sensor fault
4
Contact the professional who takes care of
maintenance of the appliance
D09
DHW S.FAILURE
SCU
Domestic hot water sensor fault
Remarks:
Heating of domestic hot water is no
longer ensured.
The load pump operates.
The load temperature of the dhw
tank is the same as the boiler.
Bad connection
Sensor fault
4
Contact the professional who takes care of
maintenance of the appliance
D11
D12
D13
ROOM S.A FAIL.
ROOM S.B FAIL.
ROOM S.C FAIL.
SCU
A room temperature sensor fault
B room temperature sensor fault
C room temperature sensor fault
Note:
The circuit concerned operates
without any influence from the room
sensor.
Bad connection
Sensor fault
4
Contact the professional who takes care of
maintenance of the appliance
D14
MC COM.FAIL
SCU
Communication failure between the
SCU PCB and the boiler radio
module
Bad connection
4
Check the link and the connectors
Boiler module failure
4
Change the boiler module
D16
SWIM.B S.FAIL
SWIM.C S.FAIL
SCU
Swimming pool sensor fault circuit
B
Swimming pool sensor fault circuit
C
Note:
Swimming pool reheating is always
done during the circuit’s comfort
period.
Bad connection
Sensor fault
4
Contact the professional who takes care of
maintenance of the appliance
D17
DHW 2 S.FAIL
SCU
Sensor fault tank 2
Bad connection.
Sensor fault.
4
Contact the professional who takes care of
maintenance of the appliance
D18
ST.TANK S.FAIL
SCU
Solar tank sensor fault
Bad connection.
Sensor fault.
4
Contact the professional who takes care of
maintenance of the appliance
D19
SOL.COL.S.FAIL
SCU
Header sensor fault
Bad connection.
Sensor fault.
4
Contact the professional who takes care of
maintenance of the appliance
D20
SOL COM.FAIL
SCU
4
Switch the boiler off and switch back on
4
Contact the professional who takes care of maintenance of the appliance
AFC 18 - AFC 24 - AFC 30
6. Troubleshooting
09/01/2014 - 300026440-001-03
36