DE DIETRICH INNOVENS MCA 35 User Manual
Page 35
Code Faults
Cause
of the
fault
Description
Checking / solution
L00
PSU FAIL
PCU
PSU PCB not connected
Bad connection
PSU PCB faulty
4
Contact the professional who takes care of
maintenance of the appliance
L01
PSU PARAM FAIL
PCU
The safety parameters are incorrect Bad connection
PSU PCB faulty
4
Contact the professional who takes care of
maintenance of the appliance
L02
DEF.OUTLET S.
PCU
The boiler flow sensor has short-
circuited
Bad connection
Sensor fault
4
Contact the professional who takes care of
maintenance of the appliance
L03
DEF.OUTLET S.
PCU
The boiler flow sensor is on an open
circuit
Bad connection
Sensor fault
4
Contact the professional who takes care of
maintenance of the appliance
L04
DEF.OUTLET S.
PCU
Boiler temp too low
Bad connection
Sensor fault
4
Contact the professional who takes care of
maintenance of the appliance
No water circulation
4
Vent the air in the heating system
4
Check the circulation (direction, pump,
valves)
4
Check the water pressure
L05
STB OUTLET
PCU
Boiler temperature too high
Bad connection
Sensor fault
4
Contact the professional who takes care of
maintenance of the appliance
No water circulation
4
Vent the air in the heating system
4
Check the circulation (direction, pump,
valves)
4
Check the water pressure
L06
BACK S.FAILURE
PCU
The return temperature sensor has
short-circuited
Bad connection
Sensor fault
4
Contact the professional who takes care of
maintenance of the appliance
L07
BACK S.FAILURE
PCU
The return temperature sensor is on
an open circuit
Bad connection
Sensor fault
4
Contact the professional who takes care of
maintenance of the appliance
L08
BACK S.FAILURE
PCU
Return temperature too low
Bad connection
Sensor fault
4
Contact the professional who takes care of
maintenance of the appliance
No water circulation
4
Vent the air in the heating system
4
Check the circulation (direction, pump,
valves)
4
Check the water pressure
MCA 35
6. Troubleshooting
24/08/2011 - 300024162-001-B
34