Changing the settings, Setting the set point temperatures, 3 changing the settings – DE DIETRICH INNOVENS PRO MCA 45 - 65 - 90 - 115 User Manual
Page 21

4.3
Changing the settings
4.3.1.
Setting the set point temperatures
To set the various heating, DHW and swimming pool temperatures,
proceed as follows:
1. Press the C key.
2. To select the desired parameter, turn the rotary button.
3. To modify the parameter, press the rotary button.
To go back to the previous display, press the key j.
4. To modify the parameter, turn the rotary button.
5. To confirm, press the rotary button.
To cancel, press key h.
Menu C
Parameter
Adjustment range Description
Factory setting
DAY TEMP. A
5 to 30 °C
Desired room temperature in comfort periods on circuit A
20 °C
NIGHT TEMP. A
5 to 30 °C
Desired room temperature in reduced periods on circuit A
16 °C
DAY TEMP. B
(1)
5 to 30 °C
Desired room temperature in comfort periods on circuit B
20 °C
NIGHT TEMP. B
(1)
5 to 30 °C
Desired room temperature in reduced periods on circuit B
16 °C
DAY TEMP. C
(1)
5 to 30 °C
Desired room temperature in comfort periods on circuit C
20 °C
NIGHT TEMP. C
(1)
5 to 30 °C
Desired room temperature in reduced periods on circuit C
16 °C
WATER TEMP.
(1)
10 to 80 °C
Desired domestic hot water temperature in the DHW circuit
55 °C
WATER T.NIGHT
(1)
(2)
10 to 80 °C
Set tank temperature, night programme
10 °C
TEMP.TANK AUX
(1)
10 to 80 °C
Desired domestic hot water temperature in the auxiliary circuit 55 °C
AUX.TANK
T.NIGHT
(1)(2)
10 to 80 °C
Set tank temperature, night programme
10 °C
DHW A TEMP.
(1)
10 to 80 °C
Desired domestic hot water temperature in circuit A
55 °C
A.TANK T.NIGHT
(1)
(2)
10 to 80 °C
Set tank temperature, night programme
10 °C
SWIMMING P.T.B
(1)
5 to 39 °C
Desired temperature for swimming pool B
20 °C
SWIMMING P.T.C
(1)
5 to 39 °C
Desired temperature for swimming pool C
20 °C
(1) The parameter is only displayed for the options, circuits or sensors actually connected.
(2) The parameter is only displayed if INSTALLATION parameter is set to EXTENDED
MODE
C002266-A
MCA 45 - 65 - 90 - 115
4. Operating the appliance - DIEMATIC iSystem
28/08/12 - 300024828-001-01
20