Technical specifications, Heat pump, 7 technical specifications – DE DIETRICH ALEZIO AWHP-V220 User Manual
Page 29: 1 technical specifications
7 Technical specifications
7.1
Technical specifications
7.1.1.
Heat pump
Conditions of use:
4
Limit operating temperatures in Hot mode:
-
Water: +18 °C / +55 °C
-
Outside air: -15 °C / +35 °C
4
Limit operating temperatures in Cooling mode:
-
Water: +18 °C / +25 °C
-
Outside air: +15 °C / +40 °C
4
Maximum operating pressure: 3 bar
AWHP-V220
4 MR
6 MR
8 MR
11 MR 11 TR
14 MR 14 TR
16 MR 16 TR
Calorific output
(1)
kW
4.1
5.73
8.08
10.87
10.37
13.07
13.07
14.95
14.95
Performance coefficient (COP)
(1)
4.3
3.93
4.03
4.23
4.15
3.95
3.95
3.82
3.82
Absorbed electrical power
(1)
kWe
0.95
1.46
2.00
2.57
2.50
3.31
3.31
3.91
3.91
Nominal amperage
(1)
A
4.3
6.8
9.3
11.2
6.7
14.8
8.8
17.7
10.1
Calorific output
(2)
kW
4
4.45
5.93
7.57
7.57
10.32
10.32
10.38
10.38
Performance coefficient (COP)
(2)
3.2
3.12
3.12
3.10
3.10
3.10
3.10
3.10
3.10
Absorbed electrical power
(2)
kWe
1.23
1.43
1.90
2.46
2.46
3.37
3.37
3.36
3.36
Cooling output
(3)
kW
3.60
5.40
7.94
10.48
10.48
11.74
11.74
11.70
11.70
Energy efficiency ratio (EER)
(4)(3)
4.65
3.80
3.99
4.68
4.68
4.43
4.43
4.40
4.40
Absorbed electrical power
(4)
kWe
0.77
1.40
1.99
2.24
2.24
2.65
2.65
2.70
2.70
Sound pressure
(5)
dB(A) 36
36
36
40
40
41
41
41
41
Nominal water flow (ΔT = 5K)
m
3
/h 0.71
1.04
1.47
1.88
1.88
2.36
2.36
2.67
2.67
Manometric height available at
nominal flow rate
mbar 450
400
200
300
300
120
120
-
-
Nominal air flow rate
m
3
/h 2100
2100
3000
6000
6000
6000
6000
6000
6000
Power voltage of the outdoor unit V
230 V~ 230 V~ 230 V~ 230 V~ 400 V3~ 230 V~ 400 V3~ 230 V~ 400 V3~
Start-up amperage
A
5
5
5
5.
3
5
3
6
3
Sound output - Inside
(6)
dB(A) 43.2
43.2
40.4
38.2
38.2
40.2
40.2
43.4
43.4
Sound output - Outside
(6)
dB(A) 63.7
63.7
65.2
65.4
65.4
66.8
66.8
69.4
69.4
R410A refrigerant
kg
2.1
2.5
3.6
5
5
5
5
5
5
Refrigeration connection (Liquid-
Gas)
inch
1/4-1/2 1/4-1/2 3/8-5/8 3/8-5/8 3/8-5/8
3/8-5/8 3/8-5/8
3/8-5/8 3/8-5/8
(1) Hot mode: Outside air temperature +7 °C, Water temperature at the outlet +35 °C. Performances in line with EN 14511-2.
(2) Hot mode: Outside air temperature +2 °C, Water temperature at the outlet +35 °C. Performances in line with EN 14511-2.
(3) Only in reversible versions
(4) Cooling mode: Outside air temperature +35 °C, Water temperature at the outlet +18 °C. Performances in line with EN 14511-2
(5) 5 m from the appliance, free field.
(6) Noise spread by the envelope - Test conducted in accordance with the standard NF EN 12102
AWHP-V220
7. Technical specifications
23/04/2013 - 300026802-001-03
28