Adjusting sub-cooling and superheat temperatures, Refrigerant filter driers, Table 13 - filter drier maximum pressure drop – AAON RL-240 User Manual
Page 47: Figure 32 - replaceable core filter/drier, Caution
![background image](/manuals/326845/47/background.png)
47
Adjusting
Sub-cooling
and
Superheat
Temperatures
The system is overcharged if the sub-cooling
temperature is too high and the evaporator is
fully loaded (low loads on the evaporator
result in increased sub-cooling) and the
evaporator
superheat
is
within
the
temperature range as shown in the table
above (high superheat results in increased
sub-cooling).
Correct an overcharged system by reducing
the amount of refrigerant in the system to
lower the sub-cooling.
The system is undercharged if the superheat
is too high and the sub-cooling is too low.
Correct an undercharged system by adding
refrigerant to the system to reduce superheat
and raise sub-cooling.
If the sub-cooling is correct and the
superheat is too high, the TXV may need
adjustment to correct the superheat.
Refrigerant Filter Driers
Each
refrigerant
circuit
contains
a
replaceable core filter drier. Replacement is
recommended when there is excessive
pressure drop across the assembly or
moisture is indicated in a liquid line sight
glass.
Table 13 - Filter Drier Maximum Pressure Drop
Circuit Loading
Max Pressure Drop
100%
5 psig
50%
2.5 psig
The filter driers are provided with pressure
taps and shutoff valves for isolation when
changing the core. For safety purposes a
service manifold must be attached prior to
filter maintenance.
Figure 32 - Replaceable Core Filter/Drier
DO NOT OVERCHARGE!
Refrigerant overcharging leads to
excess refrigerant in the condenser
coils resulting in elevated compressor
discharge pressure.
CAUTION