General information, Certification of gas heat models, Certification of steam or hot water heat models – AAON RL-240 User Manual
Page 22: Certification of electric heat models, Certification of cooling models, Codes and ordinances, Warning, Caution
22
General Information
RL Series packaged rooftop and outdoor air
handling units have been designed for
outdoor installation only.
Certification of Gas Heat Models
a. Certified as a forced air furnace with or
without cooling.
b. Certified for outdoor installation only.
c. Certified for installation on combustible
roof with a minimum of 12” high curb.
d. Certified with heat exchanger located
downstream of evaporator coil.
Certification of Steam or Hot Water Heat
Models
a. Certified as a forced air furnace with or
without cooling unit.
b. Certified for outdoor installation only.
c. Certified for installation on combustible
roof with a minimum of 12” high curb.
Certification of Electric Heat Models
a. Certified as an electric warm air furnace
with or without cooling unit.
b. Certified for outdoor installation only.
c. Certified for installation on combustible
roof with a minimum of 12” high curb.
Certification of Cooling Models
a. Certified as a commercial central air
conditioner with or without electrically
operated compressors.
b. Certified for outdoor installation only.
c. Certified for installation on combustible
roof with a minimum of 12” high curb.
d. Certified with refrigerant R-410A coils
or with chilled water cooling coils.
Codes and Ordinances
RL Series units have been tested and
certified, by ETL, in accordance with UL
Safety Standard 1995/CSA C22.2 No. 236,
ANSI Safety Standard Z83.8-2006/CSA 2.6-
2006, ANSI Z83.4-2004, and ANSI Z83.18-
2004.
System should be sized in accordance with
practices described in the American Society
of
Heating,
Refrigeration,
and
Air
Conditioning Engineers Handbooks.
Installation of RL Series units must conform
to the International Code Council (ICC)
standards of the International Mechanical
Code, the International Building Code, and
local building, plumbing, and waste water
codes. In the absence of local codes
installation must conform
to
current
National Fuel Code ANSI Z223.1/NFPA 54
or the National Gas & Propane Installation
Code CSA B149.1, and CSA B52
Mechanical
Refrigeration
Code.
All
appliances must be electrically grounded in
accordance with local codes, or in the
absence of local codes, the National Electric
Code, ANSI/NFPA 70, and/or the Canadian
Electrical Code CSA C22.1.
Improper
installation,
adjustment,
alteration, service or maintenance
can
cause
property
damage,
personal injury or loss of life. Startup
and service must be performed by a
Factory Trained Service Technician.
WARNING
These units must not be used for
heating or cooling at any time during
any phase of construction. Very low
return air temperatures, harmful
vapors, and misplacement of the
filters will damage the unit and its
efficiency.
CAUTION