002522-2HT 180210.doc

8

Do not mix non-HART compatible signals within the same cable run.


Cable should be run through a sealed metal gland rated IP66,

to avoid moisture ingress in to the

housing and provide a strong mechanical fixing. For EEx d applications the use of approved cable and
glands is a mandatory requirement

Recommended wiring practice

It is recommended that the field wiring be trimmed to length
as follows. This will then allow access to the zero and span
buttons and prevent fouling of the display cable if fitted.








Recommendations for Power supply :-

The DC power supply should have less than 2% ripple, and be able to source at least 24 mA for a single
transmitter and 100 mA for a multi-drop system, at a nominal 24 volts.


















The terminal block inside the instrument has three connections, signal, return and ground. For
convenience there is an internal ground as well as two external connections.
The Delta transmitter will run with reverse polarity and has over voltage protection as standard.



















60mm

45mm

30mm

7mm

250
ohm

RECEIVER

PSU

ADDITIONAL INSTRUMENTS

INTERNAL
CASE
GROUND

GND

+

-

+VE

-VE

GND