beautypg.com

Delta Controls 2HT User Manual

Page 14

background image

002522-2HT 180210.doc

14

CERTIFIED PRODUCTS

FLAMEPROOF


EEx d :- Model R2HT


Apparatus Certificate Number :- ITS03ATEX11187
Compliance with EN 50014:1997, EN 50018:2000

II 2 G. See Declaration of Conformity for ATEX.

EExd

II

C T4 (Tamb = -40 to +85°C)

EExd

II

C T6 (Tamb = -40 to +60°C)

Note:

Flameproof model R2HT with display fitted (see page 17, signal input code 2 or B) gas group reduced
to II B+ H

2

EExd IIB+H

2

T4 (Tamb = -40 to +85°C)

EExd IIB+ H

2

T6 (Tamb = -40 to +60°C)

INTRINSICALLY SAFE


Ex ia Approval :- Model 42HT


Apparatus Certificate Number :-

ITS03ATEX21213X

EN 60079-0:2006, EN 60079-11:2007, EN 60079-26:2007
Ga Ex ia IIC T4 (T

amb

–20 to 80

o

C)

II 1 G See Declaration of

Conformity for ATEX.

Safety Parameters :-

Ui

=

30 Volts

Ii

=

130.9 mA

Pi

=

0.66 Watts

Li

=

30 uH

Ci

=

16 nF



Special Conditions :-
1. The pressure transmitter may be fitted with an integral display or alternatively, when the blanking

plate is removed, a hand held display may be inserted into the socket provided. The removal of the
blanking cover is only permitted in a non-hazardous area.

2. The pressure transmitters intended for operation at 50 V dc do not meet the requirements of EN

50020:2002 clause 6.4.12 (Electrical Strength Test). This shall be taken into account when
installing the apparatus in a potentially explosive atmosphere.


SYSTEM

The user/installer is responsible for ensuring the safety parameters of the circuit/system are not
exceeded. Refer to IEC 60079 -14: Electrical apparatus for explosive gas atmospheres - Electrical
installations in hazardous areas (other than mines) and EN 60079 –25: Electrical apparatus for
explosive gas atmospheres - intrinsically safe systems


USA EXPLOSIONPROOF AND INTRINSICALLY SAFE




FM:-

Model F2HT


F2HT

Report Number 1B5A6.AE

Approved for Explosionproof Class I, Division 1, Groups B C & D
Dust-Ignition-Proof Class II/III, Division 1, Groups E F & G
Intrinsically Safe Class I, II, III Division 1, Groups A B C D E F & G
(

Entity requirements, Control Drawing No 2/14307, Entity Parameters: V Max =30 V, I Max = 130.9 mA, Ci = 8.85 nF,

Li = 30 µH, P Max = 0.67 W)

NEMA 4X