Schreiber Chillers 1055AC/RC HANDBOOK User Manual
Page 22
Basic Tasks
Enabling/Disabling pumps and compressors:
At the chiller:
1. Press the PRG key
2. Scroll down to the CURRENT STATUS Screen and press enter.
3. The screen will change to the RUNNING STATUS screen.
4. Press the UP arrow key once to go to the SYSTEM ON/OFF
screen.
5. Press the ENTER key to move the cursor to the different devices.
Use the UP or DOWN arrow keys to turn each device off or on.
At the terminal
1. Press the ON/OFF key.
2. Press the enter key until the cursor is at the device you wish to
enable of disable.
3. Use the UP or DOWN arrow keys to enable/disable the selected
device.
Checking Setpoints
At the chiller
1. Press the PRG key.
2. Scroll down to USER SETTINGS and press ENTER.
3. Use the arrow keys to check the temperature setpoints.
At the terminal
1. Press the SET key.
2. Use the arrow keys to check the temperature setpoints.
Checking Resetting Current Alarms
At the chiller
1. Press the ALARM key
2. Use the DOWN arrow key to scroll through the current alarms
3. Correct the alarm
4. Go to the last screen and press the ENTER key to clear the
alarm.
At the terminal- Same procedure as above.