beautypg.com

Nsg 3040-sow – Atec Teseq-NSG-3040-SOW User Manual

Page 2

background image

A d v a n c e d Te s t S o l u t i o n s f o r E M C

Parameter Value
Voltage Range

0.2 to 4.4 kV

Oscillation frequency

100 kHz and 1 MHz

Pulse repetition

1 MHz pulse: From 1/s to 600/s

1)

, default is 400/s

100 kHz pulse: From 1/s to 120/s

1)

, default is 40/s

Source impedance

150 Ω and 200 Ω

Burst duration

From 1 s to 100 s or 1 pulse to 9999 pulses or continuous –

default setting is 2 s

Rise time

75 ns

EUT AC

1 Ph 16 A, 24 to 270 Vrms, 50/60 Hz (phase - neutral), 400 Hz max.

EUT DC

16 A, 0 to 270 VDC

Coupling cap

0.5 µF

Decoupling choke

2 x ≤1.5 mH

Output Floating

Options

Type Description
WIN 3000

Control and reporting software

MD 200

Voltage calibration probe

MD 300-SOW

Current calibration probe

CDN 3425

Capacitive coupling clamp

INA XXX

Adapter for capacitive coupling clamp

INA 166

Rack mounting brackets (4HU)

© June 2013 Teseq

®

Specifications subject to change without notice.
Teseq

®

is an ISO-registered company. Its products

are designed and manufactured under the strict
quality and environmental requirements of the ISO
9001. This document has been carefully checked.
However, Teseq

®

does not assume any liability for

errors or inaccuracies.

Teseq AG
Nordstrasse 11F 4542 Luterbach Switzerland
T + 41 32 681 40 40 F + 41 32 681 40 48
[email protected]

www.teseq.com

691-309A June 2013

THE SMART 4 KV SOLUTION FOR

SLOW DAMPED OSCILLATORY WAVE TESTING

NSG 3040-SOW

Slow Damped Oscillatory Wave pulses 100 kHz and 1 MHz
Pulse conforms to IEC/EN 61000-4-18, ANSI C37.90.1, and IEC/EN 62052-11

The NSG 3040-SOW performs tests according to the following specifi cations:

1)

Pulse repetition rate is derated for voltage levels above 3 kV. Please refer to user manual.

Dimensions

449 (17.7”) x 226 (8.9”; 5 HU) x 565 mm (22.2”) (W x H x D)

Weight

approx. 25 kg (55 lbs)

Dimensions / weight