Atec T-R-DVS3 User Manual

Page 2

background image

DVS3 mk2 Specification

Output

The output of the DVS3 mk2 has four 4mm safety sockets for

phases A, B, and C and neutral. The neutral connection may be

omitted for a delta connection.

Voltage

0-133Vac phase-neutral

0-230Vac phase-phase

Current

(continuous)

200mA at 133V, 120mA at 0.1V*

Current

(5min on/ 15min off)

335mA at 133V, 200mA at 0.1V*

Voltage resolution

0.1V phase-neutral

Phase rotation

±180º

Voltage accuracy

±0.3%rdg+3d

*The current trip drops linearly between maximum and minimum output voltage. All
output ratings are based on an ambient temperature of 25°C.

Timing System

The timing system on the DVS3 mk2 is flexible and transparent

in operation. Step changes of any quantity may be generated by

typing in value using the keypad. Entering a value in this way

automatically resets and starts the timer when the change is

applied. The timer then stops on a change of state of either

contact input. More complex timing functions are handled by the

PF-F-PF mode.

Two contact inputs are provided, both of which have LEDs and a

mimic on the display to show the contact state. The contact

inputs auto-select for normally open or normally closed contacts.

A DC voltage can also be used to trigger the timer using the Vdc

contact.

Timer resolution

1ms

Timer full scale

999.999s

Timer accuracy

±0.01%rdg+2d

Contact O/C voltage

24V

Contact S/C current

20mA

Vdc input range

24-240Vdc

Protection and Safety

The DVS3 mk2 is CE marked and is designed to meet the

requirements of BS EN61010. The outputs are protected by

overcurrent and thermal trips, and the contact inputs are

protected by PTC thermistors. The phase lock current input is

fuse protected, and the voltage input is impedance protected.

An earth terminal is provided for connection to a local earth.

Supply Requirements

115V/230V±10%±10% auto-selecting, 45-65Hz 1ph 425VA max

Temperature Range

Storage -20°C to 60°C Operating 0°C to 45°C

Lead Set Specifications

1 x 3m 4 core output lead terminated in 4mm plugs

1 x 3m 2 core timer lead terminated in 4mm plugs

Dimensions Weight

380mm x 314mm x 221mm 9.1kg

Accessories

Output lead set, lead set case, mains lead, spare fuse set,

operating manual.

Optional Accessories

Printer, 133:266V step up VT box, 133:292V step up VT box.

Modes of Operation

Variable Frequency Mode

This mode allows full control of frequency, voltage and phase.

The voltage and phase may be controlled individually for each

phase or for all three phases together. All parameters are

continuously variable using the adjust control, and step changes

of any value may be generated by typing the required value on

the keypad. The new value is applied to the output when the

enter key is pressed. The timer automatically resets and starts

when a step change of value is entered, and stops if either

contact input changes state. Step changes of phase for testing

Vector Surge relays are easily generated in this mode.

Frequency resolution

0.01Hz 40.00-99.99Hz

0.1Hz 100.0-999.9Hz

Frequency accuracy

±0.01%rdg+1d

Phase resolution

0.1º

Phase accuracy

±0.3º phase to phase

Phase Lock Mode

The frequency and phase of the output are controlled by an

external reference in phase lock mode. The reference may be

the mains supply to the DVS3 mk2, an external voltage, or an

external current. This mode allows testing of directional and

distance protection in conjunction with an external current

source.

Phase lock range

45-65Hz

External voltage ref.

20-250V AC

External current ref.

0.2-5A AC

Phase resolution

0.1º

Phase accuracy

±0.3º phase to phase

±3.0º reference to output

df/dt and ROCOF (Rate Of Change Of Frequency)

Loss of mains protection often takes the form of a df/dt relay,

sensitive to the rate of change of frequency over time. The

DVS3 MK2 is able to generate a swept frequency output with

accurate rates of change of frequency between preset

frequencies. The rate of change may be continuously varied to

find the relay setting or stepped to time the relay. The output

may be set to either sweep continuously or generate single

sweeps with timing.

Frequency range

45.00-65.00Hz

Default sweep range

49.75-50.25Hz (50Hz supply)

59.75-60.25Hz (60Hz supply)

Rate of change range

0.010-3.000Hz/s

Pre-fault - Fault - Post-fault Mode

PF-F-PF mode allows extra flexibility in testing where complex

events must be timed or several sets of values must be applied

to a relay in turn. This mode allows three sets of v alues to be set

in advance (pre-fault, fault, and post-fault values). The DVS3

MK2 may be set to switch from one state to the next on a change

of contact or after a specific time. In addition, the timer may be

set to start or stop on any one of the state changes of a change

of contact state. This mode allows frequency, phase and voltage

to be changed simultaneously if required.

Note: Due to the company’s continuous research programme, the information above may change at any time without prior notificatio n. Please check that you have the most recent data on the product.

T&R Test Equipment Ltd, Keens Lane, Worplesdon, Guildford, Surrey, GU3 3LS, UK

Tel: +44 (0)1483 235757 Fax: +44 (0)1483 235759 email: [email protected]

www.trtest.com

29/04/03

DVS3 mk2 Data Sheet Rev 2