Ratio tester, Vanguard instruments company, Specifications – Atec Vanguard-ATRT-03-S2 User Manual
Page 3: Reliability through instrumentation
Vanguard Instruments Company
Reliability Through Instrumentation
TYPE
PHYSICAL SPECIFICATIONS
OPERATING VOLTAGE
MEASUREMENT METHOD
TURNS-RATIO MEASURING RANGE
TURNS-RATIO ACCURACY
TEST VOLTAGES
EXCITATION CURRENT READING RANGE
PHASE-ANGLE MEASUREMENT
DISPLAY
PRINTER
COMPUTER INTERFACES
EXTERNAL DATA STORAGE
PC SOFTWARE
INTERNAL TEST RECORD STORAGE
INTERNAL TEST PLAN STORAGE
LOAD TAP CHANGER CONTACT
SAFETY
ENVIRONMENT
HUMIDITY
ALTITUDE
CABLES
OPTIONS
WARRANTY
Portable, lightweight, automatic, 3-phase transformer turns-ratio meter
18”W x 7”H x 15”D (45.7 cm x 17.8 cm x 38.1 cm ); Weight: 20 lbs (9.0 kg)
100 – 240 Vac, 50/60 Hz
ANSI/IEEE C57.12.90
0.8 – 15,000
0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.25%. 4,000 – 15,000: ±1% @ 8Vac
0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.20%. 4,000 – 15,000: ±1% @ 40Vac
0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.15%. 4,000 – 15,000: ±1% @ 100Vac
8 Vac @ 1Amp, 40 Vac @ 0.2 Amp, 100 Vac @ 0.1 Amp
0 – 2 Amperes; Accuracy: ±0.1 mA, ±2% of reading (±1 mA)
0 – 360 Degrees; Accuracy: ±0.2 degree (±1 digit)
Back-lit LCD screen (64 x 128 dot graphic display); Viewable in bright sunlight and low-light levels
Built-in 4.5-inch wide thermal printer
One RS-232C port, One USB port
One USB Flash drive interface port; Up to 999 transformer test records can be stored on a USB Flash drive (not included)
Windows® XP/Vista-based Transformer Turns-Ratio Analyzer application is included with purchase price
Can store 112 transformer test records internally. Each record holds the test record header and up to 33 readings.
Can store 128 transformer test plans internally. Test plans can be transferred to the unit from the PC via the RS-232C/USB port
or via the USB Flash drive interface
240 Vac, 2 Amps
Designed to meet UL 61010A-1 and CAN/CSA C22.2 No. 1010.1-92 standards
Operating: -10˚ to 50˚ C (15˚ to +122˚ F); Storage: -30˚ C to 70˚ C (-22˚ to +158˚ F)
90% RH @ 40˚C (104˚F) non-condensing
2,000m (6,562 ft) to full safety specifications
One 15-foot Single-phase set, One 15-foot 3-phase set, One 25-foot extension set, One safety ground, One USB, One RS-232C, cable bag
Transportation Case
One year on parts and labor
SPECIFICATIONS
-Ratio Tester
the Tedious Procedure
of Transformer Turns-Ratio Testing
Ordering Information
ATRT-03 Series 2, Three Phase Transformer Turns-Ratio Tester
ATRT-03 S2, Cables, PC Software
Part No: ATRT-03S2
ATRT-03 S2 Carrying Case
Part No: ATRT-03S2 Case
4.5-inch Printer Paper
Part No: Paper - TP4
Rugged 16-Key
Membrane Keypad
4.5-Inch Wide
Thermal Printer
Connector for
H Terminals
LTC Control
Switches
Function
Control Knob
Emergency
Turn-Off
Connector for
X Terminals
LTC Control
Connector
USB Flash
Drive Interface
Power
Switch
USB and
RS-232C
Interfaces
Back-lit LCD Screen
(128x64 dot graphic)
Note: All specifications herein are valid at nominal voltage and ambient temperature of +25
°
C (+77
°
F). Specifications are subject to change without notice.
Thermal
Printer
Output
PC
Printer
Output
RVFeb10
▼
▼