TYPE

PHYSICAL SPECIFICATIONS

OPERATING VOLTAGE

MEASUREMENT METHOD

TURNS-RATIO MEASURING RANGE

TURNS-RATIO ACCURACY

TEST VOLTAGES

EXCITATION CURRENT READING RANGE

PHASE-ANGLE MEASUREMENT

DISPLAY

PRINTER

COMPUTER INTERFACES

EXTERNAL DATA STORAGE

PC SOFTWARE

INTERNAL TEST RECORD STORAGE

INTERNAL TEST PLAN STORAGE

LOAD TAP CHANGER CONTACT

SAFETY

ENVIRONMENT

HUMIDITY

ALTITUDE

CABLES

OPTIONS

WARRANTY

Portable, lightweight, automatic, 3-phase transformer turns-ratio meter

18”W x 7”H x 15”D (45.7 cm x 17.8 cm x 38.1 cm ); Weight: 20 lbs (9.0 kg)

100 – 240 Vac, 50/60 Hz

ANSI/IEEE C57.12.90

0.8 – 15,000

0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.25%. 4,000 – 15,000: ±1% @ 8Vac

0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.20%. 4,000 – 15,000: ±1% @ 40Vac

0.8 – 1,999: ±0.1%, 2,000 – 3,999: ±0.15%. 4,000 – 15,000: ±1% @ 100Vac

8 Vac @ 1Amp, 40 Vac @ 0.2 Amp, 100 Vac @ 0.1 Amp

0 – 2 Amperes; Accuracy: ±0.1 mA, ±2% of reading (±1 mA)

0 – 360 Degrees; Accuracy: ±0.2 degree (±1 digit)

Back-lit LCD screen (64 x 128 dot graphic display); Viewable in bright sunlight and low-light levels

Built-in 4.5-inch wide thermal printer

One RS-232C port, One USB port

One USB Flash drive interface port; Up to 999 transformer test records can be stored on a USB Flash drive (not included)

Windows® XP/Vista-based Transformer Turns-Ratio Analyzer application is included with purchase price

Can store 112 transformer test records internally. Each record holds the test record header and up to 33 readings.

Can store 128 transformer test plans internally. Test plans can be transferred to the unit from the PC via the RS-232C/USB port

or via the USB Flash drive interface

240 Vac, 2 Amps

Designed to meet UL 61010A-1 and CAN/CSA C22.2 No. 1010.1-92 standards

Operating: -10˚ to 50˚ C (15˚ to +122˚ F); Storage: -30˚ C to 70˚ C (-22˚ to +158˚ F)

90% RH @ 40˚C (104˚F) non-condensing

2,000m (6,562 ft) to full safety specifications

One 15-foot Single-phase set, One 15-foot 3-phase set, One 25-foot extension set, One safety ground, One USB, One RS-232C, cable bag

Transportation Case

One year on parts and labor

SPECIFICATIONS

-Ratio Tester

the Tedious Procedure
of Transformer Turns-Ratio Testing

Ordering Information

ATRT-03 Series 2, Three Phase Transformer Turns-Ratio Tester
ATRT-03 S2, Cables, PC Software

Part No: ATRT-03S2

ATRT-03 S2 Carrying Case

Part No: ATRT-03S2 Case

4.5-inch Printer Paper

Part No: Paper - TP4

Rugged 16-Key

Membrane Keypad

4.5-Inch Wide

Thermal Printer

Connector for

H Terminals

LTC Control

Switches

Function

Control Knob

Emergency

Turn-Off

Connector for

X Terminals

LTC Control

Connector

USB Flash

Drive Interface

Power

Switch

USB and

RS-232C

Interfaces

Back-lit LCD Screen

(128x64 dot graphic)

Note: All specifications herein are valid at nominal voltage and ambient temperature of +25

°

C (+77

°

F). Specifications are subject to change without notice.

Thermal

Printer

Output

PC

Printer

Output

RVFeb10