ATRT-01 S2 Features
Stand-alone or computer-controlled
Inexpensive
Displays ratio from 0.8 - 15,000
Calculates turn-ratio in percentage
Displays winding polarity
Displays excitation current
Size: 12”W x 9”H x 8”D
(30.5 cm x 22.9cm x 20.3cm)
Weight: 8 lbs. (3.6 kg)
ATRT-01B S2 Features
Stand-alone or computer-controlled
Battery or AC powered
Displays ratio from 0.8 - 15,000
Calculates turn-ratio in percentage
Displays winding polarity
Displays excitation current
Size: 12”W x 9”H x 8”D
(30.5 cm x 22.9cm x 20.3cm)
Weight: 9.5 lbs (4.3 kg)
ATRT-01D S2 Features
Stand-alone or computer-controlled
Battery powered (D-cells)
Displays ratio from 0.8 - 15,000
Calculates turn-ratio in percentage
Displays winding polarity
Displays excitation current
Size: 12”W x 9”H x 8”D
(30.5 cm x 22.9cm x 20.3cm)
Weight: 9.5 lbs (4.3 kg)
ATRT-01 S2
ATRT-01B S2
ATRT-01D S2
Input Power
Measurement Method
Ratio-Measuring Range
Turns-Ratio Accuracy
Test Voltages
Excitation Reading Range
Current Reading Accuracy
Display
Computer Interface
PC Software
Safety
Environment
Humidity
Altitude
Cables
Options
Warranty
120/240Vac (Selectable), 50/60Hz
ANSI/IEEE C57.12.90
0.8 – 15,000 (5-digit resolution)
0.800–1,999 (±0.1%), 2,000–3,999 (±0.25%), 4,000–15,000 (±1%)
8 Vac @ 1.0 Amp, 40 Vac @ 0.6 Amp
0 – 2 Amperes
±1 milli-amp, ±2% of reading (±1-digit)
Back-lit LCD screen (4 lines by 20 characters), viewable in bright sunlight & low-light levels
One RS-232C (19,200 baud) port
Windows® XP/Vista-based, included with purchase price
Designed to meet IEC61010 (1995), UL61010A-1, CSA-C22.2 standards
Operating: -10˚C to 50˚C (15˚F to 122˚F); Storage: -30˚ C to 70˚C (-22˚F to 158˚F)
90% RH @ 40˚C (104˚F) non-condensing
2,000m (6,562 ft) to full safety specifications
One 15-foot single-phase cable, one cable-carrying duffel bag included
Transportation case
One year on parts and labor
S
P
E
C
IF
IC
A
T
IO
N
S
S
P
E
C
IF
IC
A
T
IO
N
S
S
P
E
C
IF
IC
A
T
IO
N
S
Note: The above specifications are valid at nominal voltage and ambient temperature of +25°C (+77°F). Specifications are subject to change without notice.
Ordering Information
ATRT-01/01B/01D S2, Single Phase Transformer Turns-Ratio Testers
the Tedious Procedure
of Transformer Turns-Ratio Testing
ATRT-01 S2, Cables, PC Software
Part No. ATRT-01 S2
ATRT-01B S2, Cables, PC Software
Part No. ATRT-01B S2
ATRT-01D S2, Cables, PC Software
Part No. ATRT-01D S2
ATRT-01/01B/01D S2 Carrying Case
Part No. ATRT-01 Case
ATRT-01/01B/01D S2 Test Cable, 15-ft
Part No. ATRT-01 Cable-15ft
Input Power
Measurement Method
Ratio-Measuring Range
Turns-Ratio Accuracy
Test Voltages
Excitation Reading Range
Current Reading Accuracy
Display
Computer Interface
PC Software
Safety
Environment
Humidity
Altitude
Cables
Options
Warranty
SLA battery (90–240Vac, 50/60Hz). Delivers up to 6-hours of operation.
ANSI/IEEE C57.12.90
0.8 to 15,000 (5-digit resolution)
0.800–1,999 (±0.1%), 2,000–3,999 (±0.25%), 4,000–15,000 (±1.5%)
8 Vac @ 350 mA, 40 Vac @ 70 mA
0 – 2 Amperes
±1 Milli-amp, ±2% of reading (±1-digit)
Back-lit LCD screen (4 lines by 20 characters), viewable in bright sunlight & low-light levels
One RS-232C (19,200 baud) port
Windows® XP/Vista-based, included with purchase price
Designed to meet IEC61010 (1995), UL61010A-1, CSA-C22.2 standards
Operating: -10˚C to 50˚C (15˚F to 122˚F); Storage: -30˚ C to 70˚C (-22˚F to 158˚F)
90% RH @ 40˚C (104˚F) non-condensing
2,000m (6,562 ft) to full safety specifications
One 15-foot single-phase cable, one cable-carrying duffel bag included
Transportation case
One year on parts and labor
Input Power
Measurement Method
Ratio-Measuring Range
Turns-Ratio Accuracy
Test Voltages
Excitation Reading Range
Current Reading Accuracy
Display
Computer Interface
PC Software
Safety
Environment
Humidity
Altitude
Cables
Options
Warranty
6 D Cells (250-test capacity)
ANSI/IEEE C57.12.90
0.8 to 15,000 (5-digit resolution)
0.800–1,999 (±0.1%), 2,000–3,999 (±0.25%), 4,000–15,000 (±1.5%)
8 Vac @ 350 mA, 40 Vac @ 70 mA
0 – 2 Amperes
±1 Milli-amp, ±2% of reading (±1-digit)
Back-lit LCD screen (4 lines by 20 characters), viewable in bright sunlight & low-light levels
One RS-232C (19,200 baud) port
Windows® XP/Vista-based, included with purchase price
Designed to meet IEC61010 (1995), UL61010A-1, CSA-C22.2 standards
Operating: -10˚C to 50˚C (15˚F to 122˚F); Storage: -30˚ C to 70˚C (-22˚F to 158˚F)
90% RH @ 40˚C (104˚F) non-condensing
2,000m (6,562 ft) to full safety specificationsOne 15-foot single-phase cable, one cable-
Carrying duffel bag included
Transportation case
One year on parts and labor