Watt-muncher, Junior standard super – Atec Simplex-Watt-Muncher User Manual
Page 2
®
Watt-Muncher
DC Portable Load Bank • Page 2
Simplex, Inc.
5300 Rising Moon Road
Springfi eld, IL 62711-6228
217-483-1600
Fax 217-483-1616
www.simplexdirect.com
© 2011 Simplex, Inc. All Rights Reserved.
Printed in the USA • 1102-12.00
Design subject to change without notice.
Junior Standard Super
Capacity 70A
100A
150A
Voltage
12/24/32 V DC
12/24/32 V DC
12/24/32 V DC
(Specify One)
(Specify One)
(Specify One)
Load Steps
(1) 1A
(1) 1A
(1) 1A
(2) 2A
(2) 2A
(2) 2A
(1) 5A
(1) 5A
(1) 5A
(6) 10A
(9) 10A
(1) 10A
(2)
15A
(4)
25A
Temp. Rating
50°C Ambient
50°C Ambient
50°C Ambient
Weight
30 lbs
40 lbs
55 lbs
These load steps are
for example only. Actual
load steps depend on
specified voltage and
may vary.
Resistive Load
Simplex “Powr-Web” iron-chromium-
aluminum alloy power resistors
operating at 312°C, rated for maximum
continuous 1038°C; continuously
supported by high temperature ceramic
clad insulators
Load Step Control
Manual toggle switches, 1A resolution
Load Resistor Overvoltage/
Short Circuit Protection
One fuse per step
Cooling
Convection
Power Wiring
150°C XLP insulated
Load Termination
Positive and negative bus bar
Instrumentation
2% accuracy, 2.5” square, DC ammeter
Enclosure
16 gauge steel frame, sides and control
panel. Screened top, back and bottom.
Handles on each end. Rubber feet.
Key Features and
Dimensions
1. Ammeter
2. Metering Fuses
3. Control Toggle Switches
4. Cable Cleats
5. Carry Handles
6. Rubber Feet
7. Load Step Toggle Switches and Fuses
8. Cam-Lok Type Connectors
Options
• DC Voltmeter
• Special Terminals
• Non-Standard Voltages, Dual
Voltages
• Variable Step