PowerStar-110

110 KW Digital Load Bank
with Network Capability • Page 2

Simplex, Inc.
5300 Rising Moon Road
Springfi eld, IL 62711-6228

217-483-1600
Fax 217-483-1616
www.simplexdirect.com

© 2013 Simplex, Inc. All Rights Reserved.
Printed in the USA • 1012-08.03
Design subject to change without notice.

Dimensions and Key
Features

1. Control Compartment Cooling

Fans (2)

2. Load Element Compartment

Cooling Fans (4)

3. Load Source Connections
4. Storage Compartment for

handheld controller

5. Handles (2)
6. RS-232 and 120V connectors
7. Swivel Casters (4)

Fan/Control Power

External, 115V, 1-ph., 60Hz, 15A

service, 15’ cord with plug provided

Voltage

Dual Voltage, nominal 240/480V AC,

3-phase

208-240/416-480V AC, 3-phase, 60Hz

190-220/380-460V AC, 3-phase, 50Hz

110-240V AC, 1-phase, 50-60Hz

Load Steps

Digital load control, 5kw resolution

Frequency

50–60Hz

Duty Cycle

Continuous

Temp Rating

125° F max intake air temp

Nominal 110° F rise

Weight

125 lbs.

Options

• Vinyl Cover

• Shipping / Storage Container

Model

FLA

KW DETAIL

240V

480V

240V/480V

208/416V

240V, 1-ph

PowerStar

264

132

110

82.5

73.3

Capacity Detail

LISTED

in Atlanta, GA.