Atec Rx-Cx-Monitor User Manual
Page 2
Specifi cations are subject to change without notice.
©2013 Rx Monitoring Services Inc.
Voltage and Current Accuracy:
Low Frequency
• A/D Measurement type: True RMS calculated every half cycle
• A/D Measurement Uncertainty: AC +/- 0.1% reading +/- 0.1% full scale above 50Vrms
DC +/- 0.1% reading +/- 0.1% full scale above 50V dc Off set Error: AC/DC: 0.05Vrms
High Frequency
• A/D Measurement type: Sampled Th reshold cross 500 sample buff er per channel
• A/D Measurement Uncertainty: AC +/- 5% reading Off set Error: AC: 5V
Current:
• A/D Measurement type: True RMS calculated every cycle
• A/D Measurement Uncertainty System:
• AC +/- 0.1% reading +/- 0.1% full scale above 50Arms
• DC +/- 0.1% reading +/- 0.1% full scale above 50Adc
Off set Error: AC/DC: 1Arms
Log Types & Rates:
RMS Voltage / Current:
1 Second to 30 Minutes
10 Voltage Channels Ph-Ph, Ph-G, Ph-N & N-G
5 Current Channels { L1, L2, L3, N & G}
1 Residual Current {L1+L2+L3+N}
RMS Voltage Imbalance
Frequency:
10 Seconds to 30 Minutes
3 Voltage {L1-G, L2-G, L3-G}
Peripherals:
4 Seconds to 30 Minutes
Up to 100 Probes
Wireless DC Voltage +/- 0-600V AutoRanging
Wireless DCx Voltage {10Ch - 60dc}
Wireless DC Current {2,000A, 4,000A}
Wireless Temperature / Humidity
Wired Temperature / Humidity
Power:
10 Seconds to 30 Minutes
3 Phase Delta
{Min/Max/Average} Apparent Power(KVA), Real
power(KW), Reactive (KVAR) Power Factor (PF). Total KVA,
Total KW, Total KVAR, Total PF, Total KVAH, Total KWH, Total
KVARH, Total Demand(KVA) and Total Demand(KW)
3 Phase Wye - Split Phase - Single Pole Single Phase
{Min/Max/Average} Apparent Power(KVA), Real
power(KW), Reactive (KVAR) Power Factor (PF). Total KVA,
Total KW, Total KVAR, Total PF, Total KVAH, Total KWH, Total
KVARH, Total Demand(KVA) and Total Demand(KW)
2 Pole Single Phase
{Min/Max/Average} Apparent Power(KVA), Real
power(KW), Reactive (KVAR) Power Factor (PF). Total KVA,
Total KW, Total KVAR, Total PF, Total KVAH, Total KWH, Total
KVARH, Total Demand(KVA) and Total Demand(KW)
Harmonics:
10 Seconds to 30 Minutes
3 Ph-Ph, 3 Ph-G & 3 Current channels to the 31st.
THD:
10 Seconds to 30 Minutes
3 Ph-Ph, 3 Ph-G & 3 Current{Odd, Even, Total & Max}
Phase Angle:
10 Seconds to 30 Minutes
3 Ph-Ph, 3 Ph-G
Symmetrical Components:
10 Seconds to 30 Minutes
Voltage & Current : Magnitude, Angle & Imbalance