ELECTRICAL SPECIFICATIONS

Ground Resistance

Resolution

Accuracy

1

Range

2

0.025 - 0.25

0.002

± 1.5% ± 0.05

0.25 - 9.999

0.02

± 1.5% ± 0.1

10 - 99.99

0.04

± 2.0% ± 0.3

100 - 199.9

0.4

± 3.0% ± 1.0

200 - 400

2

± 5.0% ± 5

400 - 600

5

± 10% ± 10

600 - 1550

20

± 20%

1

Loop resistance non-inductive, external field <50 A/m,

external electrical field <1 V/m, conductor centred in jaws.

2

Resistance measurement frequency 1.667KHz

Alarm Type

Range

Resolution

High Alarm

0 - 1550

1

Low Alarm

0 - 1550

1

Leakage Current

Resolution

Accuracy

Range

3

0.200 – 1.000 mA

0.001 mA

± 2.0% ± 0.05 mA

1.00 – 10.00 mA

0.01 mA

± 2.0% ± 0.03 mA

10.0 – 100.0 mA

0.1 mA

± 2.0% ± 0.3 mA

100 – 1000 mA

1 mA

± 2.0% ± 3 mA

0.20 – 35 A

0.01 A

± 2.0% ± 0.03 A

3

Auto range, 50/60Hz, true RMS to crest factor <3.5

GENERAL SPECIFICATION

Conductor size ..................................35mm Ø approx

Battery type ......................................9V IEC 6 LR61 alkaline

Display type ......................................4 digits 9999 counts LCD

Range selection ................................Automatic within function

Overload indication ..........................OL

Power consumption..........................40 mA

Battery life ........................................3000 measurements approx

Auto power down ............................5 minutes approx

Sampling time ..................................0.5 seconds

Operating temperature ....................0 to 50º C

Storage temperature..........................-20º C to 60º C

Operating humidity ..........................Less than 85% RH

Storage humidity ..............................Less than 75% RH

Dimensions........................................276 L X 100 W X 47 H (mm)

Weight................................................750g (1.65lbs)

Data logging capacity DET10C ........116 records

Data logging capacity DET20C ........8180 records

DET10C DET20C

Earth/Ground Resistance & Leakage Current Clamp Testers

FEATURES AND BENEFITS

I

Easy and fast clamp-on operation. No need for cables

or auxiliary rods/stakes.

I

Large LCD display screen that can be read in bright

sunlight.

I

Measures ground resistance from 0.025

to 1550

.

I

Direct reading of continuity and ground loop resistance.

I

Measures ground leakage or phase current from

0.2mA to 35A.

I

Large jaw opening to accommodate a variety of

conductors.

I

Indication of high noise content that may affect

readings.

I

Lightweight...only 750g (1.65lbs), yet exceptionally

rugged for regular field use.

I

Hold function for difficult to reach installations.

I

Auto-off to save on battery power.

I

Configure high and low alarms with audible indication

for fast field checks.

I

On board storage of test results (up to 8180 records).

I

Calibration check loop to insure proper operation.

I

Rugged, yet lightweight storage case contains complete

testing kit.

I

USB interface for download of test data for later analysis

(DET20C).

The DET20C instrument is shown being used to test a pole ground.