Atec Megger-MFT1700 Series User Manual
Page 3
![background image](/manuals/319083/3/background.png)
MFT1700
Multifunction Tester
SPECIFICATION
Insulation test
Output voltage
-0% +20% at rated load or less
Voltage display
±3% ±3 digits ±0.5% of rated voltage
Short circuit current
1.5 mA nominal test current
Test current on load
1 mA at min pass values of insulation
Measurement accuracy
1000 Volts
10 kΩ ~ 999 MΩ ±3% ±2 digits
500 Volts
10 kΩ ~ 500 MΩ ±3% ±2 digits
>500
MΩ ±10% ±4 digits
250 Volts
10 kΩ ~ 250 MΩ ±3% ±2 digits
>250
MΩ ±10% ±4 digits
100 Volts
10 kΩ ~ 100 MΩ ±3% ±2 digits
>100
MΩ ±10% ±4 digits
Continuity / resistance
0.01 Ω ~ 99.9 Ω
±2% ±2 digits
100 Ω ~ 99.9 kΩ
±5% ±2 digits
Open circuit voltage
5 V ±1 V
Test current (0 Ω ~ 2 Ω)
205 mA ± 5 mA 15 mA ±5 mA
(user
selectable)
Loop test
Live to earth/neutral supply
48 V ~ 280 V (45 Hz ~ 65 Hz)
Live to live supply (not MFT1710) 48 V ~ 500 V** (45 Hz ~ 65 Hz)
L-N/L-L tests
±5% ±5 digits
L-E* tests
0.1 Ω ~ 39.9 Ω
±5% ±5 digits ± noise margin
40.0 Ω ~ 1000 Ω
±10% ±5 digits
Display range
0.01 Ω ~ 1000 Ω
Live to earth PFC range
20 kA
Live to live PSCC range
20 kA
RCD tests
Supply up to 100 mA
48 V ~ 480 V** (45 Hz ~ 65 Hz)
Supply up to 1 A
48 V ~ 280 V
RCD type
Type AC, A, S
Type B (pure dc)
No trip test (1/2xI)
–10% ~ –0%
Trip test (1xI, 2xI & 5xI)
+0% ~ +10%
Ramp test
Touch voltage (0 ~ 253 V)
+5% +15% ±0.5 V
Trip time
±1% ±1 ms
Trip current
±5%
Step increments
VAR (variable RCD selection) 10 mA ~ 50 mA 1 mA steps.
50 mA ~ 500 mA 5 mA steps
500 mA ~ 1000 mA 10 mA steps
Supply measurement
Voltage
10 V ~ 600 V (15 ~ 400 Hz) True
RMS
±3% ± 1 V ±2 digits
Phase rotation indication
L1–L2–L3 & L1–L3–L2
Frequency
15 Hz ~ 99 Hz ±0.5% ±1 digit
100 Hz ~ 400 Hz ±2.0% ±2 digit
Frequency resolution
0.1 Hz
**MFT1710 280 V
Power
MFT1710 & MFT1720:
IEC LR6 type AA alkaline
(6 cells - supplied)
MFT1730:
1.2 V NiMH (rechargeable pack
of 6 – supplied)
Mains charger for on-board
re-charging (4 hours typical)
12 V car charger (cigar lighter lead
-
optional)
Earth test
Resolution 0.01
Ω
Current
0.45 mA or 4.5 mA
Noise rejection
20 V pk/pk (7 V rms).
Max probe resistances Rp & Rc
100
kΩ @ 50 V
5
kΩ @ 25 V
2 & 3 pole method (0.01 Ω ~ 1.999 kΩ)
±2.0%
±3
digits
Current (via optional clamp meter)
±5.0%
±3
digits.
Range
0.1 mA to 200 A ac
Resolution
0.1 mA
mV Sensor input
including temperature (third party module)
±1.0%
±2
digits
Range
0.0 mV to ±199.9 mV dc
Resolution
0.1 mV
Internal memory (MFT1730)
Capacity
1000
results
Bluetooth communication
Design standards
Safety
IEC 61010-1:2010
IEC 61010-30:2010
IEC 61010-031:2008
600 V Cat III / 300 V Cat IV (Max Phase to Phase 600 V)
IEC 61557:2007 parts 1 to 10
EMC
IEC61326 edition 2 location class B
Environmental
Temperature (operational)
-10 °C ~ +55 °C
Temperature (storage)
-25 °C ~ +70 °C
Operating humidity
90% R.H. at +40 °C max
Max altitude
2000 m
Weight
1 kg (with batteries, excluding case)
Dimensions 150 mm H x 85 mm W x 235 mm D
Moisture/dust ingress protection IP54
Calibration Temperature:
+20 °C
Temperature effects
Temperature coefficient:
<0,1% per °C
* Reference conditions apply.
For test environments see service data.