Oil dielectric test sets – Atec High-Voltage-DTS-60D User Manual
Page 2
HIGH VOLTAGE, INC.
31 County Rt. 7A, Copake, NY 12516 • (518) 329-3275 • Fax: (518) 329-3271
E-Mail: [email protected] •
Web: www.hvinc.com
High Voltage, Inc. designs and manufactures high voltage test equipment for utility and industrial applications. Also available are Very Low
Frequency (VLF) high voltage AC test sets, oil dielectric test sets, AC and DC instrumented test sets, cable fault locators and other products.
1M/Jan2011
DTS-60D
DTS-100D
Input
120V, 60Hz, 7 Amps
120V, 60Hz, 7 Amps
or 230V, 50/60Hz, 4 Amps
or 230V, 50/60Hz, 4 Amps
Output
0 – 60 kVac, 800 VA
0 – 100 kVac, 800 VA
Resistive Load
Resistive Load
Output
Dual capacitively graded bushings with
Dual high voltage sections with brass
Termination
cradle contact mounting in test chamber corona spheres mounting in test chamber
Testing
Standards
Gap Gauges
0.04" / 0.08" / 0.10" ± 0.0002"
0.04" / 0.08" / 0.10" ± 0.0002"
Available
1 mm / 2 mm / 2.5 mm ± 0.005 mm
1 mm / 2 mm / 2.5 mm ± 0.005 mm
Operating
Temperature
Distortion
<5%
<5%
Kilovolt Meter 3.5 Digit LED, Scaled 0 – 60 kVac RMS
3.5 Digit LED, Scaled 0 – 100 kVac RMS
and Accuracy
2% of full scale
2% of full scale
Dimensions
15" w x 14" d x 11.5" h, 65 lbs.
18.5" w x 16.5" d x 16.5" h, 100 lbs.
and Weight
381 mm w x 356 mm d x 292 mm h, 29 kg 470 mm w x 419 mm d x 419 mm h, 45 kg
Technical Data
Our Company and Our Products
High Voltage, Inc. manufactures the most advanced test equipment available for high voltage proof and
preventive maintenance testing of electrical apparatus. All of our products are newly designed to meet
the present day needs of utilities, industrials, and testing services. Our products offer features and
specifications not found elsewhere. Our products include unique, sine-wave output Very Low
Frequency (VLF) AC Hipots, DC Insulation/HV Megohmmeter Test Sets, Aerial Lift Testers, AC
Hipots, Cable Thumpers & Radars and AC Oil Dielectric Testers.
Oil Dielectric Test Sets
DTS-60D Front Panel
DTS-100D Front Panel
ASTM D877, ASTM D1816, IEC 156 ASTM D877, ASTM D1816, IEC 156
NOTE: For 230 Volt line input models, an F is suffixed to the model number.
-14°F to 104°F -14°F to 104°F
-10°C to 40°C -10°C to 40°C