beautypg.com

Atec Hipotronics-OC60D-A-TCDE-TCVDE User Manual

Page 2

background image

European Contact

Locate your local

USA Contact

Haefely Test AG
Lehenmattstrasse 353

CH-4028 Basel
Switzerland
+ 41 61 373 4111
+ 41 61 373 4912
|

[email protected]

sales representative at

www.high-voltage-hubbell.com

Hipotronics Inc.

1650 Route 22

PO Box 414

Brewster, NY 10509 USA

+ 1 845 279 8091

+ 1 845 279 2467

|

[email protected]

Subject to technical modifications without notice.

OC60E-DS / 08.2003

Technical Specifications

Control Panel

General

Output Voltage

0 - 60 kV

Input Voltage - A

120 V, 60 Hz

Meter Accuracy

+ 2% of full scale

Input Voltage - B

220 V, 50/60 Hz

Weights and Dimensions (W x H x D, net weight, ship weight)

OC60D

16" x 13" x 15" (41 x 33 x 38 cm) 69 lbs (31 kg)

74 lbs (86 kg)

OC90D

30" x 12" x 17" (76 x 30 x 43 cm) 122 lbs (55 kg)

190 lbs (86 kg)

TCDE

6" x 4" x 3" (15 x 10 x 8 cm)

2 lbs (1 kg)

5 lbs (2 kg)

TCVDE

6" x 6" x 6" (15 x 15 x 15 cm)

5 lbs (2 kg)

10 lbs (5 kg)

TCVDE90 13" x 6" x 6" (33 x 15 x 15 cm)

11 lbs (5 kg)

20 lbs (9 kg)

OCCM-E

6" x 6" x 6" (15 x 15 x 15 cm)

4 lbs (2 kg)

8 lbs (4 kg)

Scope of Supply

Qty. 1

OC60D or OC90D Oil Tester

Qty. 1

Standard Line Cord, 7.5 ft (2.3 m)

Qty. 1

Operations Manual & Calibration Certificate

Ordering Information

System

Oil Tester, Digital 60 kV

OC60D-A, OC60D-B

Oil Tester, Digital 90 kV

OC90D-A, OC90D-B

Accessories

Digital Calibration kV meter and ramp rate meter. A 0.5

inch digital display, molded epoxy case, with 2% accuracy

at full scale. The adapter for the OC90 is included.

OCCM-E

Spare parts kit

SPK1-OC60D

SPK1-OC90D

The TCDE test cell is equipped with two one-inch diameter flat disc

electrodes; one is adjustable to provide the desired gap via a set-
screw. A standard 0.1 inch gap gauge is supplied. The TCDE is used

to test at 3000 v/s rate of rise according to ASTM D877. For use with
OC60’s.

TCDE

The TCVDE test cell is equipped with a motor-driven circulating system

0.08 inch and 0.04 inch gap gauges, and two VDE electrodes, one is

adjustable to provide the desired gap. The TCVDE is used to test
according to ASTM D1816. For use with OC60’s.

TCVDE

The TCIEC test cell is similar to the Model TCVDE cell but without a

motor. For use with OC60’s.

TCIEC

The TCCE90 test cell has VDE (mushroom) electrodes and a motor

driven circulating system for testing to ASTM D1816. For testing to

ASTM D877, disc electrodes (included) with 0.1 inch gap gauge may
be substituted. Only for use with OC90’s.

TCCE90

Test Cells

OCCM-E


TCDE ASTM D877

TCVDE ASTM D1816

TCCE90 ASTM D1816 and ASTM D877