TXL830, TXL850 and TXL870
Extra load units for TORKEL test system
APPLICATIONS
SPECIFICATIONS
Specifications are valid at nominal input voltage and an ambient
temperature of +25°C, (77°F). Specifications are subject to change
without notice.
Environment
Application field The instrument is intended for use in high-voltage
substations and industrial environments.
Temperature Operating
0°C to +40°C
Storage & transport
-40°C to +70°C
Humidity
5% – 95% RH, non-condensing
CE-marking
LVD 2006/95/EC
EMC 2004/108/EC
General
Mains voltage
100 – 240 V AC, 50 / 60 Hz
Power consumption
75 W (max)
Protection
Thermal cut-outs, automatic overload protection
Dimensions
Instrument
210 x 353 x 600 mm
Transport case
265 x 460 x 750 mm
Weight
13 kg
21.4 kg with transport case
Cable sets
for TXL830 and TXL 850 2 x 3 m, 70 mm
2
, 270 A, with cable
lug. Max. 100 V. 5 kg
for TXL870
2 x 3 m, 25 mm
2
, 110 A, with cable lug.
Max. 480 V. 3 kg
Load Section
TXL830 TXL850 TXL870
Max. voltage d.c.
28 V
56 V
140 V / 280 V
Max. current
300 A
300 A
112 A at 140 V
56 A at 280 V
Max. power
8.3 kW
16.4 kW
15.8 kW
Internal resistance, 3-position selector
Position 1
0.275
W 0.55
W 4.95
W
Current 100 A
at 27.6 V (12 x 2.3 V)
at 55.2 V (24 x 2.3 V)
-
78.5 A
at 21.6 V (12 x 1.8 V)
at 43.2 V (24 x 1.8 V)
-
50.1 A
-
-
at 248.4 V (108 x 2.3 V)
39.2 A
-
-
at 194.4 V (108 x 1.8 V)
Position 2
0.138
W 0.275
W 2.48
W
Current 200 A
at 27.6 V
at 55.2 V (24 x 2.3 V)
-
156 A
at 21.6 V
43.2 V (24 x 1.8 V)
-
Position 3
0.092
W 0.184
W 1.24
W
Current 300 A
at 27.6 V
at 55.2 V (24 x 2.3 V)
-
235 A
at 21.6 V
43.2 V (24 x 1.8 V)
-
100 A
-
-
at 124.2 V (54 x 2.3 V)
78.4 A
-
-
at 97.2 V (54 x 1.8 V)