Atec Megger-BGFT User Manual
Page 2
BGFT
BATTERY GROUND FAULT TRACER
SPECIFICATIONS
Power Source
Transmitter: 120/240 V ac, 50/60 Hz, 200 VA max.
Receiver: One 9-volt alkaline battery supplies up to 40 hours
continuous use.
Source Voltage
Variable from 0 to 50 V rms
Source Current
Load dependent from 0 to 1.7 A rms
Source Frequency
20 Hz, ±2%
Fault Resistance
1 k
Ω
to 399 k
Ω
at 50 V; bridge accuracy ±10%
Line Capacitance
0.01 to 11.1 µF; bridge accuracy ±20%
Display
Transmitter: Separate 3-digit LCD meters for volts and current
Accuracy: ±5%
Receiver: Digital meter display up to 1.999 (three gain selections)
Temperature Range
Operating: 32 to 105° F (0 to 40° C)
Storage: -5 to +130° F (-20 to +55° C)
Dimensions
Transmitter
7.5 H x 18.5 W x 14.5 D in. (19 H x 47 W x 37 D cm)
Receiver
1.5 H x 3.5 W x 7.5 D in. (4 H x 9 W x 19 D cm)
Weight
Transmitter: 35 lb (15.9 kg)
Receiver: 0.66 lb (0.3 kg)
Item (Qty)
Cat. No.
Battery Ground Fault Tracer,120/240 V ac, 50/60 Hz, CE-marked
246100B
Included Accessories
Fused source leads, 20 ft (6 m) [1 pr]
29386-3
Current transformer, 2 in. (5 cm) with leads, 4 ft (1.2 mm) [1 pr]
29999-1
AC power cord, 6 ft (1.8 m) [1]
17032-7
Feedback cable, 40 ft (12 m) [1]
29998
Padded accessory bag [1]
29996
Battery, 9 volt [1]
1482-1
Operator’s manual [1]
AVTM 246100B
Optional Accessories
Mini-CT, 0.5 in. (12 mm) with 4.25 ft (1.3 m) lead
30595
Transit case
36515
ORDERING INFORMATION
UK
Archcliffe Road, Dover
CT17 9EN England
T +44 (0) 1 304 502101
F +44 (0) 1 304 207342
[email protected]
UNITED STATES
4271 Bronze Way
Dallas, TX 75237-1019 USA
T 1 800 723 2861 (USA only)
T +1 214 333 3201
F +1 214 331 7399
[email protected]
OTHER TECHNICAL SALES OFFICES
Norristown USA, Sydney AUSTRALIA,
Toronto CANADA, Trappes FRANCE,
Kingdom of BAHRAIN, Mumbai INDIA,
Johannesburg SOUTH AFRICA, and
Conjure THAILAND
ISO STATEMENT
Registered to ISO 9001:2000 Cert. no. 10006.01
BGFT_DS_en_V11
www.megger.com
Megger is a registered trademark