Atec Megger-MIT515 User Manual
Page 3
MIT515, MIT525, MIT1025
5-kV and 10-kV dc Insulation Resistance Testers
SPECIFICATIONS
Insulation Range, Analog
100 kΩ to 10 TΩ
Insulation Range, Digital
MIT515 & MIT525:
10 kΩ to 10 TΩ
MIT1025:
10 kΩ to 20 TΩ
Test Voltages
MIT515 & MIT525:
250 V, 500 V, 1000 V, 2500 V, and 5000 V
MIT1025:
500 V, 1000 V, 2500 V, 5000 V, and 10,000 V
User Defined Test Voltages
MIT515 & MIT525:
100 V to 1 kV in 10 V steps,
1 kV to 5 kV in 25 V steps
MIT1025:
Same as above plus 5 kV to 10 kV in 25 V steps
Accuracy (23º C)
MIT515 & MIT525:
±5% to 1 TΩ, ±20% to 10 TΩ
MIT1025:
±5% to 2 TΩ, ±20% to 20 TΩ
Voltage Output Accuracy (0ºC to 30ºC)
+4% -0% ±10 V of nominal test voltage at 1 GΩ load
Voltmeter Range
30 to 660 V ac or dc, 50/60 Hz
Accuracy: ±3% ±3 V
Frequency range: 45 Hz to 65 Hz
Short Circuit Current
3 mA nominal, max. power on all loads outperforming many
5 mA testers
Insulation Alarm
100 kΩ to 1 GΩ
Current Measurement
Range:
0.01 nA to 6 mA
Accuracy
: ±5% ±0.2 nA at all voltages
Capacitance Range (above 500 V)
10 nF to 25 µF (dependent on measurement voltage)
Accuracy (23ºC): ±10% ±5 nF
Capacitor Charge
MIT515 & MIT525:
<3 s per µF at 3 mA to 5 kV
MIT1025:
<5 s per µF at 3 mA to 10 kV
Capacitor Discharge
MIT515 & MIT525:
<250 ms/µF to discharge from 5000 V to 50 V
MIT1025:
<500 ms/µF to discharge from 10,000 V to 50 V
Timer Range
Up to 99 minutes, 15 seconds minimum setting
Memory Capacity
5-1/2 hours continuous logging every 5 s.
or 33 logged PI tests
or 350 logged IR tests
Industry-Standard Tests
MIT515:
IR, IR(t), DAR, PI
MIT525 & MIT1025:
IR, IR(t), DAR, PI, SV, DD, Ramp Test
Interface
USB type B (device)
Real Time Output
USB, 1 reading/second (voltage, current and resistance)
Interference Rejection
MIT515 & MIT525:
1 mA per 250 V up to a maximum of 3 mA
MIT1025:
1 mA per 600 V up to a maximum of 3 mA
Guard Terminal
2% error guarding 500 kΩ leakage with 100 mΩ load
Voltage Input Range
85 to 265 V, 50/60 Hz, 60 VA
Battery Type
Lithium-ion, 11.1 V, 5.2 A hour, meets IEC 62133:2003
Battery Life
MIT515 & MIT525:
Typical capacity 6 hours continuous at 5 kV
with a 100 MΩ load
MIT1025:
Typical capacity 4.5 hours continuous at 10 kV with a
100 MΩ load
Battery Charge Time
2.5 hours from deep discharge, 2 hours normal discharge
30 min. quick charge: 1 hour operation at 5 kV, 100 MΩ
Safety
Meets the requirements of IEC61010-1 CAT IV 600 V
Default voltmeter warns operator of applied voltage above 50 V
EMC
Meets the requirements of IEC61326-1
Ingress Protection
IP65 (lid closed); IP40 (lid open)
Temperature Range
Operating:
-4ºF to +122ºF (-20ºC to +50ºC)
Storage:
-13ºF to +149ºF (-25ºC to +65ºC)
Humidity Range
90% RH @ 104ºF (40ºC)
Altitude
3000 m, CAT rating maintained >2000 m*
(*test load connected)
Dimensions
12 in. x 11 in. x 7 in. (315 mm x 285 mm x 181 mm)
Weight
10 lb. (4.5 kg)
Fig. 1: Quality insulation testers exhibit fast voltage rise
times to resistance levels commensurate with minimum
acceptable values, and maintain selected voltage
throughout the remaining measurement range. Below an
acceptable level of resistance, rapid voltage drop protects
the test item from exposure to high voltage, so that it may
be reclaimed by appropriate maintenance.