beautypg.com

Atec Megger-S1 Series User Manual

Page 2

background image

S1-568 and S1-1068

5 & 10 kV DC Insulation Resistance Testers

APPLICATION

The Insulation Resistance (IR) test is a quantitative test which
indicates the effectiveness of a product’s electrical insulation.
Applications include cables, transformers, motors/generators,
circuit breakers and bushings. Common insulation tests are the
“spot test”, a 1 minute IR test and a 10 minute Polarisation
Index (PI) test, where PI is the ratio R

10min

/R

1min

and temperature

independent.

ELECTRICAL SPECIFICATIONS

AC voltage input range:

90 - 264 V rms, 50/60 Hz, 100 VA

Battery:

11.1 V, 5.2 Ah meets IEC

62133:2003
Battery life S1-568:

6 hours (typical) continuous testing

at 5 kV with a 100 MΩ load

Battery life S1-1068:

4.5 hours (typical) continuous testing

at 10 kV with a 100 MΩ load

Battery charge time:

2.5 hours from deep discharge,

2 hours normal discharge

30 min. quick charge:

1 hour operation at 5 kV, 100 MΩ

Test voltages:

250 V (5 kV only), 500 V, 1000 V,

2500 V, 5000 V, 10000 V, VL

Lock test voltage:

40 V to 1 kV in 10 V steps, 1 kV to

5 kV in 25 V steps,

5 kV to 10 kV in 25 V steps

Voltage o/p accuracy:

+4%, -0%, ±10 V nominal test volt-

age

at 1GΩ load (0 °C to 30 °C)

Resistance range:

10 kΩ to 15 TΩ @ 5 kV, 10 kΩ to

35 TΩ @ 10 kV

Accuracy (23 °C):

S1-568 5000 V 2500 V

1000 V

500 V

250 V

±5% to

1 TΩ

500 GΩ 200 GΩ 100 GΩ 50 GΩ

±20% to 10 TΩ

5 TΩ

2 TΩ

1 TΩ

500 GΩ

S1-1068

10 kV

5000 V

2500 V

1000 V

500 V

250 V

±5% to

2 TΩ

1 TΩ

500 GΩ 200 GΩ 100 GΩ 50 GΩ

±20% to 20 TΩ

10 TΩ

5 TΩ

2 TΩ

1 TΩ

500 GΩ

Guard performance:

2% error guarding 500 kΩ leakage

with 100 MΩ load

Display range analogue:

100 kΩ to 10 TΩ

Display range digital:

10 kΩ to 35 TΩ

Short circuit current:

6 mA nominal


Charge current:

2 mA

Insulation alarm:

100 kΩ to 10 GΩ

Capacitor charge battery power: <2.5 s/μF to 5 kV, <5 s/μF to 10 kV

Capacitor charge AC power:

<1.5 s/μF to 5 kV, <2.7 s/μF to 10 kV

Capacitor discharge:

5 kV to 50 V: <120 ms/ μF

10 kV to 50 V: <250 ms/ μF

Capacitance range:

10 nF to 50 μF (dependant on

(> 500 V)

measurement voltage)

Capacitance accuracy (23 °C): ±10% ±5 nF
Current measurement
range:

0.01 nA to 6 mA

accuracy (23 °C):

±5% ±0.2 nA at all voltages

Interference rejection:

8 mA

Software filtering:

4 filter settings: 10s, 30s, 100s, 200s

Voltmeter range:

30 V to 660 V ac or dc, 45 Hz - 65 Hz

ELECTRICAL SPECIFICATIONS CONT

Voltmeter accuracy:

±3%, ±3 V

Timer range:

Up to 99 minutes 59 seconds, 15

second minimum setting

Memory capacity:

11 hrs logging @ 5 sec intervals

Test regimes:

IR, IR(t), DAR, PI, DD, SV, ramp test

Interfaces:

USB type B (device), Bluetooth®

Real time output:

reading/s (V, I, R) at a rate of 1 Hz

Remote control:

Remote control via USB cable only

(requires RC indicator to be in

position)

ENVIRONMENTAL SPECIFICATIONS

CATIV 600 V safety rating up to 3000 m @ 10 kV with safety plug or
guard lead inserted in guard terminal
CATIV 600 V safety rating up to 3000 m @ 5 kV
S1-1068 Altitude:

3000 m (with all three leads are

connected or when safety plug is

inserted in the guard terminal)

S1-568 Altitude:

3000 m

Operating temperature:

-20 °C to 50 °C

Storage temperature:

-25 °C to 65 °C

Humidity:

90% RH non-condensing at 40 °C

Ingress protection:

IP65 (lid closed), IP40 (lid open)

SAFETY SPECIFICATIONS

Safety: Meets the requirements of IEC 61010-1, CATIV 600 V
EMC: Meets the requirements of IEC61326-1
Dimensions:

L 315 mm x W 285 mm x H 181 mm

Weight: