S1-568 and S1-1068
5 & 10 kV DC Insulation Resistance Testers
APPLICATION
The Insulation Resistance (IR) test is a quantitative test which
indicates the effectiveness of a product’s electrical insulation.
Applications include cables, transformers, motors/generators,
circuit breakers and bushings. Common insulation tests are the
“spot test”, a 1 minute IR test and a 10 minute Polarisation
Index (PI) test, where PI is the ratio R
10min
/R
1min
and temperature
independent.
ELECTRICAL SPECIFICATIONS
AC voltage input range:
90 - 264 V rms, 50/60 Hz, 100 VA
Battery:
11.1 V, 5.2 Ah meets IEC
62133:2003
Battery life S1-568:
6 hours (typical) continuous testing
at 5 kV with a 100 MΩ load
Battery life S1-1068:
4.5 hours (typical) continuous testing
at 10 kV with a 100 MΩ load
Battery charge time:
2.5 hours from deep discharge,
2 hours normal discharge
30 min. quick charge:
1 hour operation at 5 kV, 100 MΩ
Test voltages:
250 V (5 kV only), 500 V, 1000 V,
2500 V, 5000 V, 10000 V, VL
Lock test voltage:
40 V to 1 kV in 10 V steps, 1 kV to
5 kV in 25 V steps,
5 kV to 10 kV in 25 V steps
Voltage o/p accuracy:
+4%, -0%, ±10 V nominal test volt-
age
at 1GΩ load (0 °C to 30 °C)
Resistance range:
10 kΩ to 15 TΩ @ 5 kV, 10 kΩ to
35 TΩ @ 10 kV
Accuracy (23 °C):
S1-568 5000 V 2500 V
1000 V
500 V
250 V
±5% to
1 TΩ
500 GΩ 200 GΩ 100 GΩ 50 GΩ
±20% to 10 TΩ
5 TΩ
2 TΩ
1 TΩ
500 GΩ
S1-1068
10 kV
5000 V
2500 V
1000 V
500 V
250 V
±5% to
2 TΩ
1 TΩ
500 GΩ 200 GΩ 100 GΩ 50 GΩ
±20% to 20 TΩ
10 TΩ
5 TΩ
2 TΩ
1 TΩ
500 GΩ
Guard performance:
2% error guarding 500 kΩ leakage
with 100 MΩ load
Display range analogue:
100 kΩ to 10 TΩ
Display range digital:
10 kΩ to 35 TΩ
Short circuit current:
6 mA nominal
Charge current:
2 mA
Insulation alarm:
100 kΩ to 10 GΩ
Capacitor charge battery power: <2.5 s/μF to 5 kV, <5 s/μF to 10 kV
Capacitor charge AC power:
<1.5 s/μF to 5 kV, <2.7 s/μF to 10 kV
Capacitor discharge:
5 kV to 50 V: <120 ms/ μF
10 kV to 50 V: <250 ms/ μF
Capacitance range:
10 nF to 50 μF (dependant on
(> 500 V)
measurement voltage)
Capacitance accuracy (23 °C): ±10% ±5 nF
Current measurement
range:
0.01 nA to 6 mA
accuracy (23 °C):
±5% ±0.2 nA at all voltages
Interference rejection:
8 mA
Software filtering:
4 filter settings: 10s, 30s, 100s, 200s
Voltmeter range:
30 V to 660 V ac or dc, 45 Hz - 65 Hz
ELECTRICAL SPECIFICATIONS CONT
Voltmeter accuracy:
±3%, ±3 V
Timer range:
Up to 99 minutes 59 seconds, 15
second minimum setting
Memory capacity:
11 hrs logging @ 5 sec intervals
Test regimes:
IR, IR(t), DAR, PI, DD, SV, ramp test
Interfaces:
USB type B (device), Bluetooth®
Real time output:
reading/s (V, I, R) at a rate of 1 Hz
Remote control:
Remote control via USB cable only
(requires RC indicator to be in
position)
ENVIRONMENTAL SPECIFICATIONS
CATIV 600 V safety rating up to 3000 m @ 10 kV with safety plug or
guard lead inserted in guard terminal
CATIV 600 V safety rating up to 3000 m @ 5 kV
S1-1068 Altitude:
3000 m (with all three leads are
connected or when safety plug is
inserted in the guard terminal)
S1-568 Altitude:
3000 m
Operating temperature:
-20 °C to 50 °C
Storage temperature:
-25 °C to 65 °C
Humidity:
90% RH non-condensing at 40 °C
Ingress protection:
IP65 (lid closed), IP40 (lid open)
SAFETY SPECIFICATIONS
Safety: Meets the requirements of IEC 61010-1, CATIV 600 V
EMC: Meets the requirements of IEC61326-1
Dimensions:
L 315 mm x W 285 mm x H 181 mm
Weight:
4.5 kg