SPECIFICATIONS

POWER SUPPLY

CHARGER
INPUT VOLTAGE

PULSE
CHARACTERISTICS

INPUT PROTECTION

RANGE

MEASUREMENT
ACCURACY

STORAGE

MONITOR

DIMENSIONS

WEIGHT

ENVIRONMENTAL

Battery Operated (charger included)

Model number suffix - A 120 V AC 60 Hz
Model number suffix - B 230 V AC, 50/60 Hz

Pulse Amplitude 25 V into 50
Pulse Width 100 ns to 20 µs (50ns option)

480 V AC

Time 1.28 µs to 0.66 ms
Distance 1 ft. to 1,000,000 ft.

Sample Rate = 100 MHz., Resolution = 2.5 ft. (10ns)

Stores 16 sets of 3 trace signatures or 6 pre-recorded setups with information and

10 sets of 3 trace signatures

LCD Display 7.0" diagonal

14" W x 9.5" D x 6" H (36 cm W x 24 cm D x 15 cm H)

15 lbs. (7 kg)

Operating Temperature 10° F to 122°F (-12°C to 50°C)
Storage Temperature -40° F to 140° F (-40°C to 60°C)

ACCESSORIES

• Cable Fault Locator

• HV Couplers

Cable Radar

(TDR)

Model 1130

Auxiliary HV

Equipment

(Thumper, Hipot,

or Burner)

SYSTEM

GROUND

FAULTY CABLE

HV Coupler

SAFETY GROUND

Measuring Set-Up Diagram